EA-340AC8-C01 C
12.17 kW
Defrost: Electric
Product code: EA-163EE7-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 7,975 m³/h |
|---|---|
| Air throw | 19 m |
| External surface | 67.6 m² |
| Inner volume | 20.4 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 121 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 600 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 52.0 dB(A) |
|---|---|
| Sound power | 74.3 dB(A) |
| Energy class | C |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø35 |
| EA-163EE7-C01 C | None |
|---|---|
| EA-163EE7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.44 | 5.34 | 5.29 | 5.27 | 5.23 | 5.19 | 5.14 | 5.22 | 5.55 | 6.00 | 5.86 | 5.81 | 5.74 | 5.63 |
| 5 | 7.00 | 6.94 | 6.91 | 6.91 | 6.87 | 6.81 | 6.73 | 6.80 | 7.21 | 7.80 | 7.60 | 7.53 | 7.43 | 7.29 |
| 6 | 8.61 | 8.60 | 8.62 | 8.64 | 8.62 | 8.55 | 8.46 | 8.50 | 9.01 | 9.72 | 9.44 | 9.34 | 9.19 | 8.97 |
| 7 | 10.14 | 10.25 | 10.35 | 10.45 | 10.46 | 10.39 | 10.28 | 10.31 | 10.91 | 11.78 | 11.40 | 11.26 | 11.06 | 10.75 |
| 8 | 11.61 | 11.86 | 12.08 | 12.26 | 12.33 | 12.30 | 12.20 | 12.20 | 12.90 | 13.92 | 13.47 | 13.29 | 13.03 | 12.61 |
| 9 | 13.00 | 13.41 | 13.72 | 14.02 | 14.17 | 14.20 | 14.12 | 14.15 | 14.96 | 16.15 | 15.62 | 15.41 | 15.09 | 14.58 |
| 10 | 14.27 | 14.78 | 15.29 | 15.74 | 16.01 | 16.12 | 16.08 | 16.13 | 17.07 | 18.43 | 17.85 | 17.60 | 17.24 | 16.63 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 17.846 |
| SC2 | 0 | 8 | 12.200 |
| SC3 | -18 | 7 | 10.461 |
| SC4 | -25 | 6 | 8.623 |
| SC5 | -34 | 6 | 8.615 |
| A | 1215 mm |
|---|---|
| B | 1000 mm |
| C | 1190 mm |
| F | 960 mm |
| E | 835 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø35 |
| Length | 1215 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.