EA-530AE4-C05 C
12.15 kW
Defrost: None
Product code: EA-163FC10-C08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 16,383 m³/h |
|---|---|
| Air throw | 38 m |
| External surface | 40.7 m² |
| Inner volume | 17.2 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 128 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 1,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 70.0 dB(A) |
|---|---|
| Sound power | 92.0 dB(A) |
| Energy class | E |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø35 |
| EA-163FC10-C08 C | None |
|---|---|
| EA-163FC10-C08 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.08 | 4.95 | 4.86 | 4.80 | 4.72 | 4.64 | 4.56 | 4.53 | 4.77 | 5.13 | 4.97 | 4.91 | 4.82 | 4.70 |
| 5 | 6.72 | 6.62 | 6.57 | 6.53 | 6.45 | 6.35 | 6.24 | 6.20 | 6.54 | 7.03 | 6.79 | 6.70 | 6.57 | 6.38 |
| 6 | 8.32 | 8.35 | 8.37 | 8.39 | 8.33 | 8.23 | 8.11 | 8.06 | 8.51 | 9.14 | 8.82 | 8.70 | 8.53 | 8.28 |
| 7 | 9.86 | 10.03 | 10.17 | 10.28 | 10.29 | 10.23 | 10.10 | 10.05 | 10.61 | 11.41 | 11.02 | 10.87 | 10.65 | 10.32 |
| 8 | 11.30 | 11.59 | 11.88 | 12.12 | 12.23 | 12.24 | 12.17 | 12.14 | 12.83 | 13.82 | 13.36 | 13.18 | 12.92 | 12.50 |
| 9 | 12.49 | 12.97 | 13.41 | 13.80 | 14.05 | 14.19 | 14.25 | 14.27 | 15.10 | 16.30 | 15.80 | 15.60 | 15.30 | 14.83 |
| 10 | 13.62 | 14.28 | 14.87 | 15.38 | 15.73 | 15.93 | 16.04 | 16.15 | 17.14 | 18.58 | 18.14 | 17.97 | 17.70 | 17.21 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.56 | 4.44 | 4.36 | 4.31 | 4.24 | 4.18 | 4.12 | 4.11 | 4.34 | 4.67 | 4.54 | 4.49 | 4.42 | 4.31 |
| 5 | 6.00 | 5.90 | 5.84 | 5.80 | 5.73 | 5.65 | 5.56 | 5.55 | 5.86 | 6.31 | 6.11 | 6.04 | 5.93 | 5.78 |
| 6 | 7.46 | 7.43 | 7.41 | 7.40 | 7.35 | 7.26 | 7.16 | 7.13 | 7.53 | 8.10 | 7.83 | 7.73 | 7.59 | 7.38 |
| 7 | 8.86 | 8.93 | 9.00 | 9.06 | 9.04 | 8.98 | 8.87 | 8.83 | 9.33 | 10.04 | 9.69 | 9.57 | 9.38 | 9.10 |
| 8 | 10.19 | 10.39 | 10.57 | 10.72 | 10.74 | 10.72 | 10.64 | 10.61 | 11.21 | 12.07 | 11.67 | 11.51 | 11.28 | 10.93 |
| 9 | 11.44 | 11.75 | 12.06 | 12.33 | 12.46 | 12.49 | 12.45 | 12.44 | 13.15 | 14.18 | 13.73 | 13.55 | 13.29 | 12.86 |
| 10 | 12.49 | 12.97 | 13.41 | 13.80 | 14.05 | 14.20 | 14.26 | 14.29 | 15.13 | 16.34 | 15.85 | 15.65 | 15.36 | 14.87 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 18.142 | 15.852 |
| SC2 | 0 | 8 | 12.139 | 10.606 |
| SC3 | -18 | 7 | 10.295 | 9.060 |
| SC4 | -25 | 6 | 8.371 | 7.414 |
| SC5 | -34 | 6 | 8.342 | 7.463 |
| A | 1415 mm |
|---|---|
| B | 900 mm |
| C | 1190 mm |
| F | 860 mm |
| G | 935 mm |
| E | 1035 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø35 |
| Length | 1415 mm |
|---|---|
| Width | 900 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.