EA-230BC8-C05 C
3.74 kW
Defrost: Electric
Product code: EA-230BC10-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,904 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 11.5 m² |
| Inner volume | 4.8 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 37 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 124 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 67.6 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EA-230BC10-C01 C | None |
|---|---|
| EA-230BC10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.57 | 1.53 | 1.50 | 1.49 | 1.46 | 1.44 | 1.42 | 1.42 | 1.50 | 1.62 | 1.57 | 1.55 | 1.52 | 1.49 |
| 5 | 2.07 | 2.04 | 2.03 | 2.02 | 2.00 | 1.97 | 1.94 | 1.94 | 2.05 | 2.20 | 2.13 | 2.11 | 2.07 | 2.02 |
| 6 | 2.58 | 2.57 | 2.57 | 2.58 | 2.57 | 2.54 | 2.51 | 2.51 | 2.65 | 2.85 | 2.76 | 2.72 | 2.67 | 2.60 |
| 7 | 3.08 | 3.09 | 3.12 | 3.15 | 3.16 | 3.15 | 3.12 | 3.11 | 3.29 | 3.55 | 3.43 | 3.39 | 3.32 | 3.22 |
| 8 | 3.56 | 3.62 | 3.68 | 3.74 | 3.76 | 3.76 | 3.75 | 3.75 | 3.96 | 4.28 | 4.14 | 4.09 | 4.01 | 3.88 |
| 9 | 4.01 | 4.11 | 4.22 | 4.31 | 4.37 | 4.39 | 4.39 | 4.40 | 4.65 | 5.03 | 4.88 | 4.82 | 4.73 | 4.58 |
| 10 | 4.40 | 4.55 | 4.70 | 4.83 | 4.92 | 4.99 | 5.02 | 5.05 | 5.35 | 5.78 | 5.63 | 5.56 | 5.46 | 5.30 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 5.630 |
| SC2 | 0 | 8 | 3.747 |
| SC3 | -18 | 7 | 3.157 |
| SC4 | -25 | 6 | 2.570 |
| SC5 | -34 | 6 | 2.578 |
| A | 1357 mm |
|---|---|
| B | 523 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 518 mm |
| E | 1035 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 1357 mm |
|---|---|
| Width | 523 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.