EA-230AE8-C05 C
4.16 kW
Defrost: None
Product code: EA-230BC7-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,515 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 15.7 m² |
| Inner volume | 4.8 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 30 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EA-230BC7-C05 C | None |
|---|---|
| EA-230BC7-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.76 | 1.72 | 1.70 | 1.69 | 1.67 | 1.65 | 1.63 | 1.64 | 1.74 | 1.88 | 1.83 | 1.82 | 1.79 | 1.75 |
| 5 | 2.29 | 2.27 | 2.26 | 2.26 | 2.25 | 2.22 | 2.19 | 2.20 | 2.33 | 2.52 | 2.44 | 2.42 | 2.38 | 2.33 |
| 6 | 2.82 | 2.83 | 2.85 | 2.87 | 2.86 | 2.84 | 2.81 | 2.81 | 2.98 | 3.21 | 3.10 | 3.07 | 3.01 | 2.93 |
| 7 | 3.36 | 3.40 | 3.44 | 3.49 | 3.50 | 3.49 | 3.46 | 3.46 | 3.66 | 3.95 | 3.82 | 3.77 | 3.69 | 3.57 |
| 8 | 3.85 | 3.95 | 4.03 | 4.11 | 4.15 | 4.15 | 4.13 | 4.14 | 4.38 | 4.72 | 4.57 | 4.51 | 4.41 | 4.26 |
| 9 | 4.30 | 4.44 | 4.57 | 4.70 | 4.77 | 4.82 | 4.81 | 4.83 | 5.11 | 5.52 | 5.35 | 5.27 | 5.16 | 4.99 |
| 10 | 4.70 | 4.90 | 5.08 | 5.23 | 5.33 | 5.39 | 5.42 | 5.47 | 5.80 | 6.28 | 6.13 | 6.06 | 5.93 | 5.73 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.130 |
| SC2 | 0 | 8 | 4.137 |
| SC3 | -18 | 7 | 3.494 |
| SC4 | -25 | 6 | 2.849 |
| SC5 | -34 | 6 | 2.830 |
| A | 1357 mm |
|---|---|
| B | 517 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 517.5 mm |
| E | 1035 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 1357 mm |
|---|---|
| Width | 517 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.