EA-230AE6-C05 C
4.62 kW
Defrost: Electric
Product code: EA-230BE10-C05 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,370 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 17.5 m² |
| Inner volume | 8.1 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 38 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-230BE10-C05 C | None |
|---|---|
| EA-230BE10-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.07 | 2.02 | 1.99 | 1.98 | 1.96 | 1.94 | 1.92 | 1.94 | 2.07 | 2.24 | 2.19 | 2.17 | 2.15 | 2.11 |
| 5 | 2.69 | 2.64 | 2.61 | 2.61 | 2.59 | 2.56 | 2.53 | 2.55 | 2.70 | 2.92 | 2.84 | 2.81 | 2.77 | 2.71 |
| 6 | 3.31 | 3.27 | 3.26 | 3.26 | 3.25 | 3.22 | 3.18 | 3.20 | 3.38 | 3.65 | 3.53 | 3.49 | 3.43 | 3.34 |
| 7 | 3.92 | 3.91 | 3.92 | 3.94 | 3.94 | 3.91 | 3.87 | 3.88 | 4.10 | 4.43 | 4.28 | 4.22 | 4.13 | 4.00 |
| 8 | 4.53 | 4.54 | 4.58 | 4.62 | 4.64 | 4.62 | 4.58 | 4.58 | 4.84 | 5.23 | 5.05 | 4.98 | 4.87 | 4.70 |
| 9 | 5.13 | 5.16 | 5.23 | 5.31 | 5.34 | 5.33 | 5.29 | 5.31 | 5.61 | 6.05 | 5.85 | 5.77 | 5.64 | 5.42 |
| 10 | 5.70 | 5.79 | 5.89 | 5.98 | 6.04 | 6.05 | 6.02 | 6.04 | 6.39 | 6.89 | 6.67 | 6.58 | 6.43 | 6.18 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.672 |
| SC2 | 0 | 8 | 4.582 |
| SC3 | -18 | 7 | 3.941 |
| SC4 | -25 | 6 | 3.261 |
| SC5 | -34 | 6 | 3.302 |
| A | 1357 mm |
|---|---|
| B | 567 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 517.5 mm |
| E | 1035 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1357 mm |
|---|---|
| Width | 567 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.