EA-230BE7-C01 C
5.76 kW
Defrost: None
Product code: EA-235AC10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,114 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 14.0 m² |
| Inner volume | 6.5 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 47 kg |
| Quantity | 2 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 330 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 73.0 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EA-235AC10-C01 C | None |
|---|---|
| EA-235AC10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.29 | 2.29 | 2.30 | 2.30 | 2.29 | 2.26 | 2.23 | 2.24 | 2.36 | 2.54 | 2.45 | 2.42 | 2.38 | 2.31 |
| 5 | 2.94 | 3.00 | 3.06 | 3.11 | 3.12 | 3.11 | 3.08 | 3.09 | 3.28 | 3.53 | 3.42 | 3.38 | 3.32 | 3.24 |
| 6 | 3.58 | 3.71 | 3.83 | 3.93 | 3.97 | 4.00 | 3.98 | 4.01 | 4.25 | 4.59 | 4.45 | 4.40 | 4.32 | 4.20 |
| 7 | 4.14 | 4.34 | 4.52 | 4.69 | 4.80 | 4.88 | 4.90 | 4.95 | 5.24 | 5.68 | 5.53 | 5.47 | 5.38 | 5.23 |
| 8 | 4.62 | 4.90 | 5.15 | 5.35 | 5.51 | 5.62 | 5.69 | 5.77 | 6.13 | 6.67 | 6.54 | 6.48 | 6.39 | 6.25 |
| 9 | 5.06 | 5.42 | 5.71 | 6.01 | 6.22 | 6.37 | 6.47 | 6.57 | 6.99 | 7.61 | 7.47 | 7.40 | 7.31 | 7.14 |
| 10 | 5.47 | 5.87 | 6.28 | 6.65 | 6.92 | 7.12 | 7.25 | 7.38 | 7.86 | 8.55 | 8.41 | 8.34 | 8.23 | 8.04 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 8.407 |
| SC2 | 0 | 8 | 5.767 |
| SC3 | -18 | 7 | 4.738 |
| SC4 | -25 | 6 | 3.827 |
| SC5 | -34 | 6 | 3.610 |
| A | 1357 mm |
|---|---|
| B | 523 mm |
| C | 525 mm |
| F | 345 mm |
| E1 | 517.5 mm |
| E | 1035 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 1357 mm |
|---|---|
| Width | 523 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.