EA-330AE6-C05 C
7.36 kW
Defrost: None
Product code: EA-240AC10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,713 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 17.9 m² |
| Inner volume | 8.4 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 58 kg |
| Quantity | 2 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 320 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-240AC10-C01 C | None |
|---|---|
| EA-240AC10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.93 | 2.92 | 2.92 | 2.91 | 2.88 | 2.84 | 2.79 | 2.80 | 2.96 | 3.18 | 3.07 | 3.03 | 2.97 | 2.88 |
| 5 | 3.80 | 3.86 | 3.91 | 3.95 | 3.95 | 3.93 | 3.88 | 3.89 | 4.12 | 4.44 | 4.29 | 4.24 | 4.17 | 4.06 |
| 6 | 4.65 | 4.79 | 4.91 | 5.02 | 5.06 | 5.07 | 5.04 | 5.07 | 5.36 | 5.79 | 5.60 | 5.54 | 5.44 | 5.28 |
| 7 | 5.41 | 5.64 | 5.85 | 6.04 | 6.17 | 6.24 | 6.24 | 6.28 | 6.66 | 7.19 | 6.99 | 6.91 | 6.79 | 6.60 |
| 8 | 6.06 | 6.38 | 6.68 | 6.91 | 7.10 | 7.22 | 7.29 | 7.39 | 7.85 | 8.54 | 8.36 | 8.28 | 8.17 | 7.97 |
| 9 | 6.66 | 7.09 | 7.43 | 7.78 | 8.03 | 8.20 | 8.31 | 8.43 | 8.96 | 9.75 | 9.56 | 9.48 | 9.35 | 9.14 |
| 10 | 7.21 | 7.70 | 8.19 | 8.63 | 8.95 | 9.18 | 9.33 | 9.47 | 10.08 | 10.97 | 10.77 | 10.68 | 10.55 | 10.31 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 10.774 |
| SC2 | 0 | 8 | 7.387 |
| SC3 | -18 | 7 | 6.101 |
| SC4 | -25 | 6 | 4.912 |
| SC5 | -34 | 6 | 4.684 |
| A | 1467 mm |
|---|---|
| B | 586 mm |
| C | 605 mm |
| F | 395 mm |
| E1 | 568 mm |
| E | 1135 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1467 mm |
|---|---|
| Width | 586 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.