EA-235AG7-C01 C
9.24 kW
Defrost: None
Product code: EA-240AC6-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 6,360 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 28.1 m² |
| Inner volume | 8.5 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 59 kg |
| Quantity | 2 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 320 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø28 |
| EA-240AC6-C01 C | None |
|---|---|
| EA-240AC6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.70 | 3.77 | 3.83 | 3.87 | 3.87 | 3.84 | 3.80 | 3.84 | 4.08 | 4.39 | 4.27 | 4.22 | 4.15 | 4.04 |
| 5 | 4.73 | 4.90 | 5.05 | 5.17 | 5.22 | 5.23 | 5.19 | 5.25 | 5.56 | 6.01 | 5.84 | 5.78 | 5.69 | 5.56 |
| 6 | 5.62 | 5.90 | 6.15 | 6.38 | 6.53 | 6.59 | 6.63 | 6.73 | 7.14 | 7.72 | 7.51 | 7.43 | 7.31 | 7.12 |
| 7 | 6.38 | 6.78 | 7.10 | 7.42 | 7.64 | 7.78 | 7.86 | 7.98 | 8.49 | 9.22 | 9.03 | 8.95 | 8.83 | 8.63 |
| 8 | 7.07 | 7.55 | 8.03 | 8.46 | 8.77 | 8.98 | 9.10 | 9.25 | 9.84 | 10.70 | 10.48 | 10.39 | 10.24 | 9.99 |
| 9 | ≈ 7.57 | 8.30 | 8.91 | 9.46 | 9.87 | 10.16 | 10.33 | 10.52 | 11.19 | 12.19 | 11.95 | 11.84 | 11.67 | 11.37 |
| 10 | ≈ 8.20 | 8.99 | 9.75 | 10.43 | 10.94 | 11.31 | 11.55 | 11.79 | 12.55 | 13.68 | 13.43 | 13.31 | 13.12 | 12.77 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 13.434 |
| SC2 | 0 | 8 | 9.246 |
| SC3 | -18 | 7 | 7.519 |
| SC4 | -25 | 6 | 6.153 |
| SC5 | -34 | 6 | 5.683 |
| A | 1467 mm |
|---|---|
| B | 586 mm |
| C | 605 mm |
| F | 395 mm |
| E1 | 568 mm |
| E | 1135 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø28 |
| Length | 1467 mm |
|---|---|
| Width | 586 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.