EA-530AC8-C01 C
9.19 kW
Defrost: None
Product code: EA-430AC6-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 5,247 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 32.0 m² |
| Inner volume | 9.4 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 61 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 248 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 70.0 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-430AC6-C01 C | None |
|---|---|
| EA-430AC6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.84 | 3.83 | 3.83 | 3.84 | 3.82 | 3.79 | 3.75 | 3.80 | 4.03 | 4.36 | 4.25 | 4.22 | 4.16 | 4.07 |
| 5 | 4.92 | 4.98 | 5.04 | 5.09 | 5.10 | 5.08 | 5.03 | 5.07 | 5.38 | 5.81 | 5.65 | 5.59 | 5.51 | 5.39 |
| 6 | 5.99 | 6.13 | 6.27 | 6.39 | 6.43 | 6.44 | 6.40 | 6.44 | 6.83 | 7.38 | 7.15 | 7.07 | 6.94 | 6.75 |
| 7 | 6.94 | 7.19 | 7.42 | 7.63 | 7.77 | 7.84 | 7.82 | 7.87 | 8.34 | 9.01 | 8.75 | 8.64 | 8.49 | 8.24 |
| 8 | 7.78 | 8.13 | 8.46 | 8.72 | 8.92 | 9.04 | 9.09 | 9.19 | 9.76 | 10.60 | 10.35 | 10.24 | 10.09 | 9.79 |
| 9 | 8.56 | 9.04 | 9.42 | 9.81 | 10.07 | 10.24 | 10.33 | 10.45 | 11.10 | 12.05 | 11.78 | 11.67 | 11.49 | 11.18 |
| 10 | 9.28 | 9.83 | 10.38 | 10.86 | 11.21 | 11.44 | 11.56 | 11.72 | 12.45 | 13.52 | 13.23 | 13.10 | 12.90 | 12.55 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 13.232 |
| SC2 | 0 | 8 | 9.192 |
| SC3 | -18 | 7 | 7.696 |
| SC4 | -25 | 6 | 6.268 |
| SC5 | -34 | 6 | 6.024 |
| A | 2107 mm |
|---|---|
| B | 523 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 455 mm |
| E2 | 438 mm |
| E | 1785 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 2107 mm |
|---|---|
| Width | 523 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.