EA-430AC6-C01 C
9.19 kW
Defrost: None
Product code: EA-530AC8-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,616 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 28.9 m² |
| Inner volume | 11.0 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 71 kg |
| Quantity | 5 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 310 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 71.1 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-530AC8-C01 C | None |
|---|---|
| EA-530AC8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.74 | 3.73 | 3.74 | 3.75 | 3.73 | 3.69 | 3.64 | 3.68 | 3.91 | 4.21 | 4.09 | 4.04 | 3.98 | 3.88 |
| 5 | 4.80 | 4.87 | 4.95 | 5.01 | 5.02 | 5.00 | 4.95 | 4.99 | 5.29 | 5.72 | 5.54 | 5.48 | 5.40 | 5.28 |
| 6 | 5.85 | 6.02 | 6.17 | 6.31 | 6.36 | 6.38 | 6.35 | 6.40 | 6.78 | 7.32 | 7.10 | 7.02 | 6.89 | 6.70 |
| 7 | 6.79 | 7.06 | 7.32 | 7.56 | 7.71 | 7.79 | 7.79 | 7.85 | 8.33 | 9.00 | 8.74 | 8.64 | 8.49 | 8.25 |
| 8 | 7.60 | 7.99 | 8.35 | 8.63 | 8.86 | 9.00 | 9.07 | 9.19 | 9.77 | 10.62 | 10.38 | 10.28 | 10.14 | 9.86 |
| 9 | 8.35 | 8.86 | 9.29 | 9.71 | 10.01 | 10.21 | 10.32 | 10.46 | 11.12 | 12.09 | 11.84 | 11.73 | 11.56 | 11.28 |
| 10 | 9.04 | 9.63 | 10.22 | 10.74 | 11.13 | 11.39 | 11.55 | 11.74 | 12.48 | 13.57 | 13.31 | 13.19 | 13.01 | 12.69 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 13.310 |
| SC2 | 0 | 8 | 9.192 |
| SC3 | -18 | 7 | 7.628 |
| SC4 | -25 | 6 | 6.172 |
| SC5 | -34 | 6 | 5.889 |
| A | 2407 mm |
|---|---|
| B | 523 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 428 mm |
| E2 | 410 mm |
| E | 2085 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 2407 mm |
|---|---|
| Width | 523 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.