EA-235AE8-C01 C
7.86 kW
Defrost: None
Product code: EA-240AC8-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 6,565 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 21.7 m² |
| Inner volume | 8.4 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 58 kg |
| Quantity | 2 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 320 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-240AC8-C01 C | None |
|---|---|
| EA-240AC8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.15 | 3.15 | 3.16 | 3.16 | 3.14 | 3.10 | 3.05 | 3.07 | 3.24 | 3.48 | 3.37 | 3.33 | 3.27 | 3.18 |
| 5 | 4.06 | 4.14 | 4.22 | 4.28 | 4.29 | 4.27 | 4.22 | 4.24 | 4.49 | 4.84 | 4.69 | 4.63 | 4.56 | 4.44 |
| 6 | 4.95 | 5.13 | 5.29 | 5.43 | 5.49 | 5.50 | 5.48 | 5.51 | 5.84 | 6.30 | 6.10 | 6.03 | 5.92 | 5.76 |
| 7 | 5.71 | 5.98 | 6.23 | 6.46 | 6.61 | 6.68 | 6.72 | 6.81 | 7.23 | 7.82 | 7.61 | 7.52 | 7.39 | 7.18 |
| 8 | 6.38 | 6.76 | 7.06 | 7.37 | 7.59 | 7.73 | 7.81 | 7.91 | 8.41 | 9.14 | 8.95 | 8.87 | 8.75 | 8.55 |
| 9 | 6.99 | 7.44 | 7.89 | 8.29 | 8.58 | 8.77 | 8.89 | 9.02 | 9.60 | 10.44 | 10.23 | 10.14 | 10.01 | 9.78 |
| 10 | 7.55 | 8.11 | 8.67 | 9.17 | 9.55 | 9.80 | 9.97 | 10.14 | 10.79 | 11.74 | 11.53 | 11.43 | 11.28 | 11.02 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 11.531 |
| SC2 | 0 | 8 | 7.911 |
| SC3 | -18 | 7 | 6.525 |
| SC4 | -25 | 6 | 5.291 |
| SC5 | -34 | 6 | 4.994 |
| A | 1467 mm |
|---|---|
| B | 586 mm |
| C | 605 mm |
| F | 395 mm |
| E1 | 568 mm |
| E | 1135 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1467 mm |
|---|---|
| Width | 586 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.