EA-430AC7-C05 C
8.11 kW
Defrost: None
Product code: EA-530AC10-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 6,044 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 23.9 m² |
| Inner volume | 11.0 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 55 kg |
| Quantity | 5 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 600 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-530AC10-C05 C | None |
|---|---|
| EA-530AC10-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.32 | 3.30 | 3.29 | 3.29 | 3.26 | 3.23 | 3.18 | 3.22 | 3.42 | 3.69 | 3.59 | 3.55 | 3.49 | 3.40 |
| 5 | 4.28 | 4.31 | 4.35 | 4.39 | 4.39 | 4.36 | 4.31 | 4.36 | 4.62 | 4.99 | 4.83 | 4.78 | 4.71 | 4.61 |
| 6 | 5.23 | 5.31 | 5.42 | 5.51 | 5.56 | 5.56 | 5.52 | 5.56 | 5.89 | 6.37 | 6.17 | 6.10 | 5.99 | 5.82 |
| 7 | 6.11 | 6.30 | 6.49 | 6.65 | 6.74 | 6.77 | 6.76 | 6.81 | 7.22 | 7.81 | 7.58 | 7.49 | 7.35 | 7.12 |
| 8 | 6.91 | 7.20 | 7.47 | 7.72 | 7.89 | 8.00 | 8.02 | 8.08 | 8.56 | 9.28 | 9.03 | 8.92 | 8.76 | 8.49 |
| 9 | 7.63 | 8.01 | 8.37 | 8.70 | 8.90 | 9.05 | 9.13 | 9.25 | 9.83 | 10.68 | 10.45 | 10.34 | 10.19 | 9.89 |
| 10 | 8.29 | 8.79 | 9.20 | 9.61 | 9.91 | 10.11 | 10.22 | 10.38 | 11.03 | 11.98 | 11.74 | 11.63 | 11.45 | 11.15 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 11.741 |
| SC2 | 0 | 8 | 8.076 |
| SC3 | -18 | 7 | 6.695 |
| SC4 | -25 | 6 | 5.415 |
| SC5 | -34 | 6 | 5.255 |
| A | 2407 mm |
|---|---|
| B | 517 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 4275 mm |
| E2 | 410 mm |
| E | 2085 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 2407 mm |
|---|---|
| Width | 567 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.