EA-530AE8-C01 C
11.54 kW
Defrost: Electric
Product code: EA-240AE7-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,716 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 36.7 m² |
| Inner volume | 12.6 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 69 kg |
| Quantity | 2 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 320 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | B |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø35 |
| EA-240AE7-C01 C | None |
|---|---|
| EA-240AE7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.89 | 4.85 | 4.83 | 4.83 | 4.79 | 4.73 | 4.65 | 4.74 | 5.05 | 5.46 | 5.32 | 5.28 | 5.21 | 5.09 |
| 5 | 6.28 | 6.32 | 6.37 | 6.41 | 6.39 | 6.33 | 6.23 | 6.31 | 6.70 | 7.23 | 7.00 | 6.92 | 6.82 | 6.68 |
| 6 | 7.67 | 7.81 | 7.92 | 8.04 | 8.07 | 8.03 | 7.93 | 7.99 | 8.46 | 9.13 | 8.81 | 8.69 | 8.52 | 8.25 |
| 7 | 8.95 | 9.22 | 9.48 | 9.69 | 9.78 | 9.77 | 9.69 | 9.74 | 10.31 | 11.14 | 10.74 | 10.58 | 10.35 | 9.97 |
| 8 | 10.09 | 10.49 | 10.87 | 11.19 | 11.40 | 11.48 | 11.48 | 11.53 | 12.20 | 13.18 | 12.73 | 12.54 | 12.26 | 11.79 |
| 9 | 11.13 | 11.68 | 12.18 | 12.57 | 12.84 | 12.99 | 13.02 | 13.16 | 13.95 | 15.11 | 14.69 | 14.50 | 14.22 | 13.66 |
| 10 | 12.09 | 12.80 | 13.38 | 13.93 | 14.30 | 14.52 | 14.59 | 14.75 | 15.64 | 16.94 | 16.48 | 16.27 | 15.95 | 15.38 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 16.483 |
| SC2 | 0 | 8 | 11.531 |
| SC3 | -18 | 7 | 9.738 |
| SC4 | -25 | 6 | 7.918 |
| SC5 | -34 | 6 | 7.709 |
| A | 1467 mm |
|---|---|
| B | 636 mm |
| C | 605 mm |
| F | 445 mm |
| E1 | 568 mm |
| E | 1135 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø35 |
| Length | 1467 mm |
|---|---|
| Width | 636 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.