EA-630BE10-C05 C
11.25 kW
Defrost: Electric
Product code: EA-240AG10-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,498 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 35.8 m² |
| Inner volume | 16.6 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 83 kg |
| Quantity | 2 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 320 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | B |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø35 |
| EA-240AG10-C01 C | None |
|---|---|
| EA-240AG10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.73 | 4.74 | 4.76 | 4.78 | 4.76 | 4.71 | 4.64 | 4.74 | 5.04 | 5.45 | 5.31 | 5.27 | 5.21 | 5.12 |
| 5 | 5.99 | 6.10 | 6.19 | 6.28 | 6.30 | 6.27 | 6.19 | 6.27 | 6.65 | 7.19 | 6.96 | 6.88 | 6.77 | 6.60 |
| 6 | 7.24 | 7.42 | 7.62 | 7.79 | 7.87 | 7.87 | 7.81 | 7.88 | 8.35 | 9.03 | 8.72 | 8.60 | 8.42 | 8.13 |
| 7 | 8.38 | 8.72 | 9.04 | 9.31 | 9.46 | 9.50 | 9.46 | 9.54 | 10.10 | 10.93 | 10.56 | 10.41 | 10.18 | 9.80 |
| 8 | 9.42 | 9.90 | 10.35 | 10.74 | 10.99 | 11.12 | 11.12 | 11.22 | 11.89 | 12.84 | 12.44 | 12.26 | 11.99 | 11.53 |
| 9 | 10.34 | 10.97 | 11.55 | 12.06 | 12.33 | 12.54 | 12.61 | 12.78 | 13.56 | 14.70 | 14.32 | 14.14 | 13.83 | 13.29 |
| 10 | 11.18 | 11.97 | 12.61 | 13.25 | 13.69 | 13.97 | 14.09 | 14.30 | 15.17 | 16.45 | 16.04 | 15.84 | 15.53 | 14.98 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 16.038 |
| SC2 | 0 | 8 | 11.221 |
| SC3 | -18 | 7 | 9.383 |
| SC4 | -25 | 6 | 7.618 |
| SC5 | -34 | 6 | 7.251 |
| A | 1467 mm |
|---|---|
| B | 686 mm |
| C | 605 mm |
| F | 495 mm |
| E1 | 568 mm |
| E | 1135 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø35 |
| Length | 1467 mm |
|---|---|
| Width | 686 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.