EA-340AE4-C01 C
17.69 kW
Defrost: Electric
Product code: EA-245AE6-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 9,305 m³/h |
|---|---|
| Air throw | 16 m |
| External surface | 57.5 m² |
| Inner volume | 17.0 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 93 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 980 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | D |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-245AE6-C01 C | None |
|---|---|
| EA-245AE6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.37 | 7.38 | 7.40 | 7.41 | 7.37 | 7.28 | 7.17 | 7.31 | 7.77 | 8.40 | 8.18 | 8.10 | 7.97 | 7.78 |
| 5 | 9.48 | 9.60 | 9.75 | 9.88 | 9.89 | 9.83 | 9.69 | 9.82 | 10.41 | 11.25 | 10.90 | 10.78 | 10.62 | 10.40 |
| 6 | 11.44 | 11.81 | 12.14 | 12.41 | 12.53 | 12.50 | 12.39 | 12.50 | 13.24 | 14.30 | 13.82 | 13.63 | 13.37 | 12.96 |
| 7 | 13.15 | 13.72 | 14.24 | 14.69 | 14.97 | 15.06 | 15.08 | 15.26 | 16.18 | 17.49 | 16.92 | 16.69 | 16.35 | 15.81 |
| 8 | 14.69 | 15.49 | 16.12 | 16.75 | 17.16 | 17.39 | 17.46 | 17.66 | 18.75 | 20.34 | 19.80 | 19.57 | 19.22 | 18.66 |
| 9 | 16.11 | 17.06 | 18.00 | 18.82 | 19.36 | 19.69 | 19.83 | 20.09 | 21.32 | 23.12 | 22.53 | 22.27 | 21.87 | 21.19 |
| 10 | 17.24 | 18.60 | 19.79 | 20.83 | 21.54 | 21.99 | 22.21 | 22.52 | 23.91 | 25.93 | 25.30 | 25.00 | 24.55 | 23.76 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 25.300 |
| SC2 | 0 | 8 | 17.662 |
| SC3 | -18 | 7 | 14.819 |
| SC4 | -25 | 6 | 12.142 |
| SC5 | -34 | 6 | 11.532 |
| A | 1767 mm |
|---|---|
| B | 640 mm |
| C | 645 mm |
| F | 445 mm |
| E1 | 718 mm |
| E | 1435 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 1767 mm |
|---|---|
| Width | 640 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.