EA-163GC7-C08 C
16.90 kW
Defrost: Electric
Product code: EA-245AE7-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 9,526 m³/h |
|---|---|
| Air throw | 16 m |
| External surface | 50.1 m² |
| Inner volume | 17.0 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 92 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 980 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | D |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-245AE7-C01 C | None |
|---|---|
| EA-245AE7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.96 | 6.94 | 6.92 | 6.91 | 6.85 | 6.75 | 6.63 | 6.75 | 7.16 | 7.72 | 7.49 | 7.40 | 7.28 | 7.09 |
| 5 | 8.98 | 9.10 | 9.21 | 9.29 | 9.28 | 9.19 | 9.05 | 9.15 | 9.69 | 10.46 | 10.12 | 10.01 | 9.85 | 9.63 |
| 6 | 10.96 | 11.26 | 11.53 | 11.75 | 11.80 | 11.77 | 11.64 | 11.73 | 12.42 | 13.40 | 12.92 | 12.75 | 12.50 | 12.12 |
| 7 | 12.70 | 13.19 | 13.65 | 14.04 | 14.29 | 14.40 | 14.34 | 14.40 | 15.25 | 16.48 | 15.92 | 15.70 | 15.37 | 14.85 |
| 8 | 14.22 | 14.93 | 15.57 | 16.06 | 16.42 | 16.62 | 16.67 | 16.85 | 17.88 | 19.40 | 18.88 | 18.66 | 18.33 | 17.72 |
| 9 | 15.63 | 16.46 | 17.33 | 18.07 | 18.56 | 18.85 | 18.96 | 19.19 | 20.37 | 22.09 | 21.52 | 21.27 | 20.89 | 20.25 |
| 10 | 16.92 | 18.01 | 19.09 | 20.03 | 20.67 | 21.07 | 21.26 | 21.55 | 22.88 | 24.81 | 24.20 | 23.92 | 23.48 | 22.74 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 24.199 |
| SC2 | 0 | 8 | 16.853 |
| SC3 | -18 | 7 | 14.158 |
| SC4 | -25 | 6 | 11.529 |
| SC5 | -34 | 6 | 11.040 |
| A | 1767 mm |
|---|---|
| B | 640 mm |
| C | 645 mm |
| F | 445 mm |
| E1 | 718 mm |
| E | 1435 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 1767 mm |
|---|---|
| Width | 640 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.