EA-340AC4-C01 C
15.41 kW
Defrost: None
Product code: EA-245AE8-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 9,749 m³/h |
|---|---|
| Air throw | 17 m |
| External surface | 44.5 m² |
| Inner volume | 17.0 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 92 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 980 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | D |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-245AE8-C01 C | None |
|---|---|
| EA-245AE8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.27 | 6.20 | 6.15 | 6.11 | 6.04 | 5.94 | 5.82 | 5.90 | 6.25 | 6.72 | 6.51 | 6.43 | 6.32 | 6.15 |
| 5 | 8.17 | 8.21 | 8.25 | 8.28 | 8.24 | 8.14 | 8.00 | 8.07 | 8.54 | 9.21 | 8.91 | 8.81 | 8.67 | 8.46 |
| 6 | 10.06 | 10.25 | 10.42 | 10.53 | 10.56 | 10.50 | 10.36 | 10.42 | 11.03 | 11.89 | 11.47 | 11.31 | 11.10 | 10.77 |
| 7 | 11.80 | 12.18 | 12.53 | 12.81 | 12.95 | 12.95 | 12.83 | 12.90 | 13.65 | 14.73 | 14.21 | 14.01 | 13.71 | 13.24 |
| 8 | 13.31 | 13.86 | 14.37 | 14.82 | 15.10 | 15.20 | 15.23 | 15.40 | 16.33 | 17.65 | 17.07 | 16.83 | 16.48 | 15.90 |
| 9 | 14.69 | 15.44 | 16.05 | 16.66 | 17.06 | 17.28 | 17.37 | 17.56 | 18.64 | 20.21 | 19.69 | 19.47 | 19.13 | 18.56 |
| 10 | 15.96 | 16.86 | 17.74 | 18.52 | 19.04 | 19.36 | 19.51 | 19.75 | 20.96 | 22.73 | 22.17 | 21.92 | 21.54 | 20.88 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 22.174 |
| SC2 | 0 | 8 | 15.395 |
| SC3 | -18 | 7 | 12.882 |
| SC4 | -25 | 6 | 10.416 |
| SC5 | -34 | 6 | 10.117 |
| A | 1767 mm |
|---|---|
| B | 640 mm |
| C | 645 mm |
| F | 445 mm |
| E1 | 718 mm |
| E | 1435 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 1767 mm |
|---|---|
| Width | 640 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.