EA-345AC8-C01 C
18.20 kW
Defrost: None
Product code: EA-245AG8-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 8,850 m³/h |
|---|---|
| Air throw | 15 m |
| External surface | 59.3 m² |
| Inner volume | 22.7 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 113 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 980 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø42 |
| EA-245AG8-C01 C | None |
|---|---|
| EA-245AG8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.59 | 7.64 | 7.68 | 7.72 | 7.69 | 7.61 | 7.49 | 7.64 | 8.13 | 8.79 | 8.56 | 8.48 | 8.39 | 8.20 |
| 5 | 9.63 | 9.84 | 10.03 | 10.19 | 10.23 | 10.18 | 10.05 | 10.18 | 10.80 | 11.67 | 11.29 | 11.16 | 10.98 | 10.72 |
| 6 | 11.63 | 12.03 | 12.40 | 12.70 | 12.82 | 12.84 | 12.73 | 12.85 | 13.62 | 14.72 | 14.21 | 14.02 | 13.73 | 13.27 |
| 7 | 13.41 | 14.03 | 14.60 | 15.10 | 15.42 | 15.54 | 15.49 | 15.61 | 16.54 | 17.90 | 17.27 | 17.03 | 16.65 | 16.00 |
| 8 | 14.95 | 15.81 | 16.59 | 17.27 | 17.63 | 17.88 | 17.96 | 18.19 | 19.30 | 20.93 | 20.37 | 20.10 | 19.63 | 18.82 |
| 9 | 16.37 | 17.48 | 18.38 | 19.26 | 19.85 | 20.21 | 20.36 | 20.64 | 21.90 | 23.75 | 23.13 | 22.82 | 22.34 | 21.50 |
| 10 | 17.66 | 18.92 | 20.17 | 21.25 | 22.03 | 22.52 | 22.75 | 23.09 | 24.52 | 26.59 | 25.91 | 25.56 | 25.02 | 24.05 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 25.912 |
| SC2 | 0 | 8 | 18.189 |
| SC3 | -18 | 7 | 15.249 |
| SC4 | -25 | 6 | 12.397 |
| SC5 | -34 | 6 | 11.728 |
| A | 1767 mm |
|---|---|
| B | 690 mm |
| C | 645 mm |
| F | 495 mm |
| E1 | 718 mm |
| E | 1435 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø42 |
| Length | 1767 mm |
|---|---|
| Width | 690 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.