EA-163GD4-C08 C
24.00 kW
Defrost: Electric
Product code: EA-250AG8-C09 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 11,970 m³/h |
|---|---|
| Air throw | 18 m |
| External surface | 76.8 m² |
| Inner volume | 30.2 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 143 kg |
| Quantity | 2 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 1,420 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.0 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| EA-250AG8-C09 C | None |
|---|---|
| EA-250AG8-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 10.27 | 10.12 | 10.03 | 9.97 | 9.86 | 9.71 | 9.54 | 9.69 | 10.29 | 11.11 | 10.81 | 10.70 | 10.54 | 10.29 |
| 5 | 13.30 | 13.28 | 13.29 | 13.31 | 13.24 | 13.08 | 12.86 | 12.97 | 13.75 | 14.83 | 14.35 | 14.19 | 13.97 | 13.66 |
| 6 | 16.25 | 16.43 | 16.61 | 16.78 | 16.78 | 16.66 | 16.43 | 16.51 | 17.47 | 18.83 | 18.16 | 17.91 | 17.56 | 17.01 |
| 7 | 19.17 | 19.58 | 19.96 | 20.30 | 20.40 | 20.35 | 20.14 | 20.21 | 21.37 | 23.06 | 22.20 | 21.87 | 21.38 | 20.59 |
| 8 | 21.81 | 22.49 | 23.15 | 23.74 | 24.05 | 24.09 | 23.92 | 24.02 | 25.40 | 27.41 | 26.45 | 26.05 | 25.45 | 24.46 |
| 9 | 24.14 | 25.11 | 26.01 | 26.81 | 27.29 | 27.48 | 27.52 | 27.76 | 29.43 | 31.80 | 30.75 | 30.28 | 29.59 | 28.42 |
| 10 | 26.31 | 27.60 | 28.79 | 29.72 | 30.37 | 30.76 | 30.86 | 31.16 | 33.03 | 35.74 | 34.78 | 34.33 | 33.64 | 32.46 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 34.776 |
| SC2 | 0 | 8 | 24.016 |
| SC3 | -18 | 7 | 20.341 |
| SC4 | -25 | 6 | 16.613 |
| SC5 | -34 | 6 | 16.312 |
| A | 2087 mm |
|---|---|
| B | 740 mm |
| C | 685 mm |
| F | 545 mm |
| E1 | 868 mm |
| E | 1735 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 2087 mm |
|---|---|
| Width | 690 mm |
| Height | 685 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.