EA-263ED10-C01 C
19.87 kW
Defrost: None
Product code: EA-263EC7-C06 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 18,012 m³/h |
|---|---|
| Air throw | 23 m |
| External surface | 90.1 m² |
| Inner volume | 27.5 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 168 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 890 rpm |
| Power | 1,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 76.5 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø42 |
| EA-263EC7-C06 C | None |
|---|---|
| EA-263EC7-C06 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.53 | 8.37 | 8.29 | 8.24 | 8.17 | 8.09 | 8.00 | 8.07 | 8.53 | 9.21 | 8.98 | 8.89 | 8.77 | 8.59 |
| 5 | 11.10 | 11.01 | 10.95 | 10.94 | 10.88 | 10.77 | 10.65 | 10.70 | 11.33 | 12.23 | 11.90 | 11.78 | 11.61 | 11.36 |
| 6 | 13.61 | 13.68 | 13.75 | 13.82 | 13.80 | 13.69 | 13.54 | 13.57 | 14.36 | 15.49 | 15.03 | 14.86 | 14.62 | 14.27 |
| 7 | 16.04 | 16.31 | 16.56 | 16.77 | 16.78 | 16.74 | 16.60 | 16.62 | 17.58 | 18.97 | 18.38 | 18.16 | 17.85 | 17.35 |
| 8 | 18.33 | 18.78 | 19.24 | 19.64 | 19.83 | 19.87 | 19.78 | 19.81 | 20.97 | 22.63 | 21.94 | 21.67 | 21.27 | 20.65 |
| 9 | 20.23 | 20.97 | 21.65 | 22.27 | 22.66 | 22.88 | 22.96 | 23.08 | 24.44 | 26.42 | 25.64 | 25.33 | 24.87 | 24.13 |
| 10 | 22.06 | 23.07 | 23.98 | 24.79 | 25.32 | 25.63 | 25.77 | 25.98 | 27.56 | 29.89 | 29.19 | 28.90 | 28.47 | 27.70 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.54 | 7.39 | 7.31 | 7.27 | 7.22 | 7.17 | 7.10 | 7.18 | 7.61 | 8.23 | 8.05 | 7.98 | 7.88 | 7.74 |
| 5 | 9.74 | 9.63 | 9.57 | 9.56 | 9.51 | 9.43 | 9.34 | 9.39 | 9.95 | 10.76 | 10.48 | 10.38 | 10.25 | 10.05 |
| 6 | 11.99 | 11.95 | 11.96 | 11.99 | 11.95 | 11.87 | 11.76 | 11.79 | 12.48 | 13.47 | 13.09 | 12.95 | 12.75 | 12.46 |
| 7 | 14.16 | 14.26 | 14.38 | 14.51 | 14.52 | 14.45 | 14.32 | 14.34 | 15.17 | 16.38 | 15.88 | 15.70 | 15.43 | 15.02 |
| 8 | 16.25 | 16.53 | 16.80 | 17.04 | 17.10 | 17.08 | 16.98 | 17.00 | 17.98 | 19.41 | 18.81 | 18.58 | 18.26 | 17.72 |
| 9 | 18.22 | 18.65 | 19.11 | 19.51 | 19.71 | 19.77 | 19.71 | 19.73 | 20.88 | 22.56 | 21.88 | 21.62 | 21.21 | 20.59 |
| 10 | 19.90 | 20.59 | 21.23 | 21.82 | 22.20 | 22.41 | 22.46 | 22.52 | 23.85 | 25.77 | 25.04 | 24.73 | 24.28 | 23.56 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 29.191 | 25.040 |
| SC2 | 0 | 8 | 19.810 | 16.995 |
| SC3 | -18 | 7 | 16.805 | 14.522 |
| SC4 | -25 | 6 | 13.749 | 11.964 |
| SC5 | -34 | 6 | 13.647 | 11.999 |
| A | 2015 mm |
|---|---|
| B | 900 mm |
| C | 1190 mm |
| F | 860 mm |
| E1 | 818 mm |
| E | 1635 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø42 |
| Length | 2015 mm |
|---|---|
| Width | 900 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.