EA-535AE8-C01 C
19.91 kW
Defrost: None
Product code: EA-263ED10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 17,315 m³/h |
|---|---|
| Air throw | 23 m |
| External surface | 81.2 m² |
| Inner volume | 32.9 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 189 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 1,200 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 77.3 dB(A) |
| Energy class | C |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø35 |
| EA-263ED10-C01 C | None |
|---|---|
| EA-263ED10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.30 | 8.29 | 8.29 | 8.30 | 8.25 | 8.16 | 8.05 | 8.11 | 8.58 | 9.25 | 8.97 | 8.87 | 8.72 | 8.50 |
| 5 | 10.63 | 10.78 | 10.90 | 11.00 | 10.99 | 10.93 | 10.81 | 10.85 | 11.49 | 12.39 | 12.01 | 11.88 | 11.68 | 11.39 |
| 6 | 12.80 | 13.17 | 13.48 | 13.74 | 13.85 | 13.84 | 13.74 | 13.76 | 14.57 | 15.72 | 15.23 | 15.05 | 14.78 | 14.37 |
| 7 | 14.81 | 15.45 | 15.91 | 16.38 | 16.64 | 16.74 | 16.71 | 16.79 | 17.78 | 19.21 | 18.63 | 18.41 | 18.06 | 17.52 |
| 8 | 16.53 | 17.40 | 18.18 | 18.87 | 19.33 | 19.60 | 19.73 | 19.87 | 21.06 | 22.79 | 22.15 | 21.89 | 21.49 | 20.84 |
| 9 | 18.09 | 19.23 | 20.26 | 21.17 | 21.79 | 22.19 | 22.40 | 22.65 | 24.05 | 26.11 | 25.53 | 25.28 | 24.90 | 24.23 |
| 10 | 19.52 | 20.95 | 22.26 | 23.40 | 24.21 | 24.75 | 25.06 | 25.37 | 26.95 | 29.27 | 28.65 | 28.37 | 27.95 | 27.23 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 28.647 |
| SC2 | 0 | 8 | 19.866 |
| SC3 | -18 | 7 | 16.502 |
| SC4 | -25 | 6 | 13.484 |
| SC5 | -34 | 6 | 12.895 |
| A | 2015 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| E1 | 818 mm |
| E | 1635 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø35 |
| Length | 2015 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.