EA-250BG10-C10 C
27.17 kW
Defrost: Electric
Product code: EA-263ED10-C11 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 32,451 m³/h |
|---|---|
| Air throw | 42 m |
| External surface | 81.4 m² |
| Inner volume | 33.9 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 223 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 5,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 71.0 dB(A) |
|---|---|
| Sound power | 94.0 dB(A) |
| Energy class | E |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø42 |
| EA-263ED10-C11 C | None |
|---|---|
| EA-263ED10-C11 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 11.21 | 10.94 | 10.74 | 10.59 | 10.39 | 10.19 | 9.98 | 9.93 | 10.45 | 11.22 | 10.84 | 10.70 | 10.51 | 10.22 |
| 5 | 14.85 | 14.72 | 14.62 | 14.50 | 14.32 | 14.07 | 13.79 | 13.74 | 14.50 | 15.55 | 14.99 | 14.78 | 14.48 | 14.03 |
| 6 | 18.37 | 18.51 | 18.62 | 18.68 | 18.58 | 18.35 | 18.04 | 17.96 | 18.96 | 20.36 | 19.62 | 19.35 | 18.96 | 18.38 |
| 7 | 21.70 | 22.10 | 22.50 | 22.82 | 22.90 | 22.78 | 22.53 | 22.47 | 23.73 | 25.51 | 24.59 | 24.25 | 23.75 | 22.97 |
| 8 | 24.53 | 25.34 | 26.08 | 26.73 | 27.12 | 27.31 | 27.16 | 27.15 | 28.70 | 30.93 | 29.88 | 29.47 | 28.87 | 27.91 |
| 9 | 27.12 | 28.29 | 29.34 | 30.26 | 30.83 | 31.14 | 31.25 | 31.46 | 33.37 | 36.15 | 35.24 | 34.87 | 34.21 | 33.08 |
| 10 | 29.52 | 31.09 | 32.50 | 33.71 | 34.51 | 34.98 | 35.20 | 35.47 | 37.63 | 40.79 | 39.79 | 39.38 | 38.76 | 37.73 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 9.91 | 9.66 | 9.48 | 9.35 | 9.20 | 9.04 | 8.88 | 8.94 | 9.43 | 10.14 | 9.83 | 9.72 | 9.56 | 9.33 |
| 5 | 13.10 | 12.88 | 12.76 | 12.67 | 12.50 | 12.29 | 12.06 | 12.12 | 12.83 | 13.81 | 13.37 | 13.21 | 12.97 | 12.61 |
| 6 | 16.23 | 16.22 | 16.22 | 16.21 | 16.07 | 15.86 | 15.58 | 15.61 | 16.50 | 17.75 | 17.13 | 16.91 | 16.61 | 16.16 |
| 7 | 19.25 | 19.48 | 19.68 | 19.84 | 19.81 | 19.63 | 19.34 | 19.34 | 20.44 | 21.99 | 21.19 | 20.89 | 20.46 | 19.82 |
| 8 | 22.11 | 22.56 | 23.02 | 23.40 | 23.53 | 23.45 | 23.21 | 23.22 | 24.54 | 26.43 | 25.46 | 25.10 | 24.57 | 23.72 |
| 9 | 24.55 | 25.36 | 26.11 | 26.77 | 27.16 | 27.33 | 27.16 | 27.21 | 28.77 | 31.04 | 29.96 | 29.54 | 28.91 | 27.89 |
| 10 | 26.83 | 27.95 | 28.97 | 29.86 | 30.41 | 30.69 | 30.75 | 30.97 | 32.83 | 35.56 | 34.56 | 34.07 | 33.36 | 32.20 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 39.794 | 34.555 |
| SC2 | 0 | 8 | 27.150 | 23.218 |
| SC3 | -18 | 7 | 22.876 | 19.850 |
| SC4 | -25 | 6 | 18.615 | 16.216 |
| SC5 | -34 | 6 | 18.424 | 16.251 |
| A | 2015 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| E1 | 818 mm |
| E | 1635 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø42 |
| Length | 2015 mm |
|---|---|
| Width | 950 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.