EA-250AE4-C10 C
25.63 kW
Defrost: None
Product code: EA-263EE7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 15,922 m³/h |
|---|---|
| Air throw | 21 m |
| External surface | 135.2 m² |
| Inner volume | 41.2 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 203 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 1,200 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 77.4 dB(A) |
| Energy class | C |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø42 |
| EA-263EE7-C01 C | None |
|---|---|
| EA-263EE7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 11.15 | 11.07 | 11.05 | 11.05 | 11.00 | 10.91 | 10.80 | 10.96 | 11.64 | 12.60 | 12.30 | 12.19 | 12.02 | 11.78 |
| 5 | 14.28 | 14.33 | 14.38 | 14.47 | 14.46 | 14.36 | 14.21 | 14.35 | 15.22 | 16.46 | 16.01 | 15.85 | 15.63 | 15.31 |
| 6 | 17.26 | 17.55 | 17.82 | 18.05 | 18.11 | 18.04 | 17.86 | 17.98 | 19.05 | 20.57 | 19.95 | 19.73 | 19.40 | 18.90 |
| 7 | 20.09 | 20.68 | 21.20 | 21.55 | 21.76 | 21.78 | 21.65 | 21.76 | 23.04 | 24.89 | 24.11 | 23.81 | 23.37 | 22.66 |
| 8 | 22.73 | 23.55 | 24.36 | 25.06 | 25.45 | 25.60 | 25.53 | 25.66 | 27.17 | 29.38 | 28.47 | 28.10 | 27.56 | 26.67 |
| 9 | 24.93 | 26.14 | 27.24 | 28.21 | 28.83 | 29.18 | 29.30 | 29.58 | 31.38 | 33.94 | 32.94 | 32.51 | 31.88 | 30.82 |
| 10 | 27.02 | 28.60 | 30.02 | 31.26 | 32.07 | 32.56 | 32.78 | 33.11 | 35.13 | 38.09 | 37.15 | 36.74 | 36.12 | 35.06 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 37.152 |
| SC2 | 0 | 8 | 25.656 |
| SC3 | -18 | 7 | 21.660 |
| SC4 | -25 | 6 | 17.817 |
| SC5 | -34 | 6 | 17.350 |
| A | 2015 mm |
|---|---|
| B | 1000 mm |
| C | 1190 mm |
| F | 960 mm |
| E1 | 818 mm |
| E | 1635 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø42 |
| Length | 2015 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.