EA-263GE10-C08 C
40.78 kW
Defrost: Electric
Product code: EA-263GC4-C08 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 32,876 m³/h |
|---|---|
| Air throw | 42 m |
| External surface | 216.9 m² |
| Inner volume | 43.7 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 269 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 3,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 72.0 dB(A) |
|---|---|
| Sound power | 95.0 dB(A) |
| Energy class | E |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EA-263GC4-C08 C | None |
|---|---|
| EA-263GC4-C08 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 17.29 | 17.04 | 16.94 | 16.90 | 16.80 | 16.66 | 16.52 | 16.58 | 17.54 | 18.95 | 18.48 | 18.31 | 18.07 | 17.71 |
| 5 | 22.34 | 22.40 | 22.47 | 22.54 | 22.45 | 22.27 | 22.05 | 22.07 | 23.36 | 25.21 | 24.52 | 24.28 | 23.93 | 23.42 |
| 6 | 27.28 | 27.78 | 28.07 | 28.41 | 28.48 | 28.38 | 28.15 | 28.13 | 29.76 | 32.09 | 31.15 | 30.81 | 30.32 | 29.58 |
| 7 | 31.58 | 32.53 | 33.40 | 34.19 | 34.66 | 34.82 | 34.67 | 34.67 | 36.68 | 39.57 | 38.39 | 37.95 | 37.30 | 36.29 |
| 8 | 35.43 | 36.86 | 38.15 | 39.28 | 39.99 | 40.40 | 40.57 | 40.84 | 43.33 | 46.96 | 45.89 | 45.47 | 44.79 | 43.54 |
| 9 | 39.01 | 41.00 | 42.77 | 44.31 | 45.31 | 45.91 | 46.22 | 46.55 | 49.40 | 53.57 | 52.35 | 51.86 | 51.14 | 49.96 |
| 10 | 42.32 | 44.91 | 47.24 | 49.24 | 50.60 | 51.44 | 51.91 | 52.34 | 55.56 | 60.27 | 58.93 | 58.38 | 57.56 | 56.20 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 15.42 | 15.21 | 15.10 | 15.07 | 15.00 | 14.91 | 14.80 | 14.91 | 15.81 | 17.10 | 16.71 | 16.57 | 16.37 | 16.07 |
| 5 | 19.94 | 19.86 | 19.85 | 19.86 | 19.79 | 19.66 | 19.49 | 19.56 | 20.72 | 22.39 | 21.83 | 21.63 | 21.34 | 20.92 |
| 6 | 24.38 | 24.59 | 24.80 | 24.99 | 24.99 | 24.86 | 24.64 | 24.67 | 26.11 | 28.19 | 27.38 | 27.10 | 26.69 | 26.07 |
| 7 | 28.65 | 29.14 | 29.68 | 30.14 | 30.32 | 30.29 | 30.10 | 30.12 | 31.87 | 34.40 | 33.38 | 33.00 | 32.45 | 31.60 |
| 8 | 32.28 | 33.27 | 34.20 | 35.04 | 35.56 | 35.85 | 35.81 | 35.85 | 37.94 | 40.98 | 39.77 | 39.31 | 38.62 | 37.54 |
| 9 | 35.65 | 37.09 | 38.39 | 39.55 | 40.28 | 40.70 | 40.88 | 41.15 | 43.66 | 47.33 | 46.22 | 45.78 | 45.08 | 43.78 |
| 10 | 38.81 | 40.74 | 42.48 | 43.99 | 44.98 | 45.58 | 45.87 | 46.20 | 49.02 | 53.14 | 51.92 | 51.41 | 50.65 | 49.40 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 58.928 | 51.915 |
| SC2 | 0 | 8 | 40.839 | 35.848 |
| SC3 | -18 | 7 | 34.409 | 30.241 |
| SC4 | -25 | 6 | 28.071 | 24.795 |
| SC5 | -34 | 6 | 27.432 | 24.461 |
| A | 3015 mm |
|---|---|
| B | 900 mm |
| C | 1190 mm |
| F | 860 mm |
| G | 935 mm |
| E1 | 1318 mm |
| E | 2635 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 3015 mm |
|---|---|
| Width | 900 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.