EA-263EG4-C06 C
35.37 kW
Defrost: Electric
Product code: EA-263GD10-C08 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 33,600 m³/h |
|---|---|
| Air throw | 43 m |
| External surface | 131.7 m² |
| Inner volume | 53.9 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 286 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 3,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 72.0 dB(A) |
|---|---|
| Sound power | 95.0 dB(A) |
| Energy class | E |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| EA-263GD10-C08 C | None |
|---|---|
| EA-263GD10-C08 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 15.37 | 14.93 | 14.63 | 14.44 | 14.22 | 13.99 | 13.77 | 13.72 | 14.47 | 15.57 | 15.10 | 14.93 | 14.68 | 14.32 |
| 5 | 20.20 | 19.85 | 19.61 | 19.45 | 19.22 | 18.93 | 18.63 | 18.52 | 19.55 | 21.02 | 20.34 | 20.09 | 19.74 | 19.21 |
| 6 | 25.12 | 24.95 | 24.87 | 24.82 | 24.61 | 24.33 | 23.98 | 23.82 | 25.14 | 27.03 | 26.11 | 25.77 | 25.29 | 24.56 |
| 7 | 29.83 | 29.99 | 30.16 | 30.33 | 30.26 | 30.04 | 29.68 | 29.51 | 31.15 | 33.51 | 32.36 | 31.93 | 31.30 | 30.34 |
| 8 | 34.33 | 34.90 | 35.30 | 35.77 | 35.92 | 35.83 | 35.57 | 35.42 | 37.42 | 40.30 | 38.95 | 38.43 | 37.68 | 36.48 |
| 9 | 38.32 | 39.30 | 40.25 | 41.14 | 41.62 | 41.72 | 41.58 | 41.50 | 43.87 | 47.33 | 45.84 | 45.25 | 44.38 | 42.97 |
| 10 | 41.97 | 43.39 | 44.71 | 45.92 | 46.69 | 47.14 | 47.33 | 47.56 | 50.43 | 54.47 | 52.87 | 52.22 | 51.26 | 49.67 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 13.65 | 13.24 | 12.99 | 12.84 | 12.67 | 12.50 | 12.34 | 12.33 | 13.03 | 14.06 | 13.66 | 13.52 | 13.32 | 13.01 |
| 5 | 17.87 | 17.49 | 17.26 | 17.12 | 16.93 | 16.71 | 16.47 | 16.42 | 17.35 | 18.69 | 18.13 | 17.92 | 17.63 | 17.21 |
| 6 | 22.20 | 21.92 | 21.74 | 21.68 | 21.51 | 21.28 | 20.99 | 20.89 | 22.07 | 23.76 | 22.99 | 22.71 | 22.31 | 21.71 |
| 7 | 26.41 | 26.34 | 26.36 | 26.43 | 26.31 | 26.10 | 25.81 | 25.67 | 27.12 | 29.19 | 28.23 | 27.86 | 27.34 | 26.53 |
| 8 | 30.48 | 30.71 | 30.96 | 31.22 | 31.24 | 31.10 | 30.83 | 30.68 | 32.41 | 34.92 | 33.77 | 33.32 | 32.68 | 31.65 |
| 9 | 34.38 | 34.95 | 35.42 | 35.92 | 36.13 | 36.11 | 35.92 | 35.81 | 37.86 | 40.82 | 39.51 | 39.00 | 38.24 | 37.02 |
| 10 | 37.98 | 38.82 | 39.75 | 40.62 | 41.06 | 41.19 | 41.10 | 41.05 | 43.42 | 46.86 | 45.45 | 44.87 | 44.01 | 42.60 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 52.872 | 45.445 |
| SC2 | 0 | 8 | 35.417 | 30.682 |
| SC3 | -18 | 7 | 30.324 | 26.402 |
| SC4 | -25 | 6 | 24.865 | 21.743 |
| SC5 | -34 | 6 | 25.116 | 22.165 |
| A | 3015 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| G | 985 mm |
| E1 | 1318 mm |
| E | 2635 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 3015 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.