EA-480GG7-C01 C
132.64 kW
Defrost: None
Product code: EA-291AI4-C04 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 48,928 m³/h |
|---|---|
| Air throw | 45 m |
| External surface | 1,002.4 m² |
| Inner volume | 198.7 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 882 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 5,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 70.0 dB(A) |
|---|---|
| Sound power | 94.0 dB(A) |
| Energy class | C |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø66,7 |
| EA-291AI4-C04 C | None |
|---|---|
| EA-291AI4-C04 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 60.36 | 60.45 | 60.80 | 61.26 | 61.34 | 61.10 | 60.60 | 61.71 | 65.63 | 71.20 | 69.60 | 69.05 | 68.30 | 67.22 |
| 5 | 75.47 | 76.31 | 77.25 | 78.17 | 78.38 | 78.18 | 77.53 | 78.42 | 83.21 | 90.14 | 87.63 | 86.71 | 85.37 | 83.32 |
| 6 | 89.71 | 91.71 | 93.59 | 95.26 | 95.98 | 95.93 | 95.18 | 95.87 | 101.57 | 109.82 | 106.43 | 105.11 | 103.15 | 100.03 |
| 7 | 103.10 | 106.55 | 109.20 | 111.88 | 113.31 | 113.67 | 113.07 | 113.72 | 120.39 | 130.15 | 126.00 | 124.32 | 121.82 | 117.71 |
| 8 | 115.57 | 119.95 | 124.42 | 128.37 | 130.75 | 131.65 | 131.26 | 131.98 | 139.70 | 150.91 | 146.21 | 144.20 | 141.16 | 136.04 |
| 9 | 126.01 | 132.50 | 138.42 | 143.58 | 146.87 | 148.54 | 148.91 | 150.09 | 159.03 | 171.95 | 166.73 | 164.39 | 160.84 | 154.80 |
| 10 | 136.12 | 144.39 | 151.91 | 158.43 | 162.74 | 165.04 | 165.81 | 167.17 | 177.14 | 191.58 | 186.39 | 184.00 | 180.32 | 173.84 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 47.56 | 47.29 | 47.37 | 47.64 | 47.67 | 47.47 | 47.04 | 48.05 | 51.15 | 55.57 | 54.29 | 53.85 | 53.23 | 52.35 |
| 5 | 59.14 | 59.20 | 59.57 | 60.08 | 60.19 | 59.95 | 59.38 | 60.16 | 63.86 | 69.25 | 67.25 | 66.51 | 65.41 | 63.69 |
| 6 | 70.74 | 71.25 | 72.01 | 72.75 | 73.03 | 72.81 | 72.13 | 72.72 | 77.03 | 83.40 | 80.72 | 79.66 | 78.07 | not rated |
| 7 | 81.71 | 82.97 | 84.31 | 85.61 | 86.14 | 85.94 | 85.16 | 85.62 | 90.59 | 97.87 | 94.60 | 93.25 | not rated | not rated |
| 8 | 92.19 | 94.36 | 96.45 | 98.36 | 99.26 | 99.29 | 98.48 | 98.79 | 104.45 | 112.67 | 108.84 | not rated | not rated | not rated |
| 9 | 102.07 | 105.33 | 108.36 | 110.66 | 112.09 | 112.37 | 111.73 | 112.06 | 118.45 | 127.67 | 123.41 | not rated | not rated | not rated |
| 10 | 111.34 | 115.42 | 119.47 | 122.98 | 125.01 | 125.64 | 125.15 | 125.52 | 132.66 | 142.92 | not rated | not rated | not rated | not rated |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 186.390 | — |
| SC2 | 0 | 8 | 131.984 | 98.786 |
| SC3 | -18 | 7 | 112.589 | 85.906 |
| SC4 | -25 | 6 | 93.586 | 72.012 |
| SC5 | -34 | 6 | 90.251 | 70.929 |
| A | 3638 mm |
|---|---|
| C | 1587 mm |
| F | 1132 mm |
| G | 1250 mm |
| E1 | 1635 mm |
| E2 | 1600 mm |
| E | 3235 mm |
| H | 1434 mm |
| I | 1750 mm |
| D IN | 2 x Ø42 |
| D OUT | 2 x Ø66,7 |
| Length | 3638 mm |
|---|---|
| Width | 1434 mm |
| Height | 1750 mm |
Our engineers answer with a selection for your conditions.