EA-235AE10-C01 C
7.33 kW
Defrost: Electric
Product code: EA-330AE6-C05 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,011 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 35.6 m² |
| Inner volume | 10.4 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 47 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 360 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 45.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-330AE6-C05 C | None |
|---|---|
| EA-330AE6-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.27 | 3.26 | 3.27 | 3.29 | 3.29 | 3.26 | 3.22 | 3.30 | 3.52 | 3.82 | 3.73 | 3.70 | 3.67 | 3.62 |
| 5 | 4.12 | 4.16 | 4.21 | 4.25 | 4.26 | 4.24 | 4.19 | 4.26 | 4.52 | 4.90 | 4.75 | 4.70 | 4.62 | 4.51 |
| 6 | 4.94 | 5.04 | 5.14 | 5.23 | 5.27 | 5.26 | 5.21 | 5.26 | 5.57 | 6.03 | 5.83 | 5.75 | 5.63 | 5.44 |
| 7 | 5.75 | 5.92 | 6.08 | 6.22 | 6.29 | 6.30 | 6.25 | 6.30 | 6.67 | 7.21 | 6.96 | 6.86 | 6.70 | 6.46 |
| 8 | 6.49 | 6.75 | 6.99 | 7.19 | 7.31 | 7.34 | 7.30 | 7.36 | 7.78 | 8.41 | 8.13 | 8.01 | 7.82 | 7.52 |
| 9 | 7.15 | 7.49 | 7.81 | 8.09 | 8.26 | 8.35 | 8.34 | 8.42 | 8.91 | 9.61 | 9.31 | 9.17 | 8.96 | 8.61 |
| 10 | 7.76 | 8.20 | 8.61 | 8.92 | 9.15 | 9.27 | 9.31 | 9.40 | 9.97 | 10.78 | 10.48 | 10.33 | 10.11 | 9.71 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 10.476 |
| SC2 | 0 | 8 | 7.356 |
| SC3 | -18 | 7 | 6.249 |
| SC4 | -25 | 6 | 5.141 |
| SC5 | -34 | 6 | 4.964 |
| A | 1657 mm |
|---|---|
| B | 567 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 450.5 mm |
| E2 | 434 mm |
| E | 1335 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1657 mm |
|---|---|
| Width | 567 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.