EA-530AC8-C05 C
8.60 kW
Defrost: None
Product code: EA-335AC10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 7,669 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 20.9 m² |
| Inner volume | 9.8 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 65 kg |
| Quantity | 3 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 495 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø28 |
| EA-335AC10-C01 C | None |
|---|---|
| EA-335AC10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.40 | 3.45 | 3.49 | 3.53 | 3.53 | 3.50 | 3.46 | 3.48 | 3.69 | 3.96 | 3.84 | 3.79 | 3.72 | 3.61 |
| 5 | 4.34 | 4.49 | 4.60 | 4.71 | 4.76 | 4.78 | 4.75 | 4.79 | 5.08 | 5.48 | 5.32 | 5.26 | 5.18 | 5.05 |
| 6 | 5.19 | 5.46 | 5.69 | 5.89 | 6.03 | 6.10 | 6.10 | 6.16 | 6.54 | 7.07 | 6.88 | 6.81 | 6.70 | 6.52 |
| 7 | 5.92 | 6.28 | 6.61 | 6.86 | 7.07 | 7.22 | 7.31 | 7.42 | 7.89 | 8.59 | 8.42 | 8.35 | 8.25 | 8.07 |
| 8 | 6.58 | 7.05 | 7.44 | 7.83 | 8.12 | 8.32 | 8.45 | 8.60 | 9.15 | 9.97 | 9.79 | 9.71 | 9.59 | 9.38 |
| 9 | 7.17 | 7.71 | 8.26 | 8.76 | 9.14 | 9.41 | 9.60 | 9.78 | 10.41 | 11.35 | 11.16 | 11.08 | 10.94 | 10.70 |
| 10 | ≈ 7.56 | 8.37 | 9.04 | 9.66 | 10.13 | 10.48 | 10.73 | 10.95 | 11.68 | 12.74 | 12.55 | 12.45 | 12.31 | 12.03 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 12.546 |
| SC2 | 0 | 8 | 8.597 |
| SC3 | -18 | 7 | 6.958 |
| SC4 | -25 | 6 | 5.687 |
| SC5 | -34 | 6 | 5.257 |
| A | 1857 mm |
|---|---|
| B | 523 mm |
| C | 525 mm |
| F | 345 mm |
| E1 | 517.5 mm |
| E2 | 500 mm |
| E | 1535 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø28 |
| Length | 1857 mm |
|---|---|
| Width | 523 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.