EA-430AE7-C05 C
9.02 kW
Defrost: Electric
Product code: EA-335AC8-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 7,492 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 25.4 m² |
| Inner volume | 9.8 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 66 kg |
| Quantity | 3 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 495 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø28 |
| EA-335AC8-C01 C | None |
|---|---|
| EA-335AC8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.55 | 3.62 | 3.68 | 3.72 | 3.72 | 3.70 | 3.65 | 3.68 | 3.90 | 4.20 | 4.07 | 4.02 | 3.95 | 3.84 |
| 5 | 4.53 | 4.71 | 4.86 | 4.97 | 5.03 | 5.05 | 5.02 | 5.07 | 5.38 | 5.81 | 5.64 | 5.57 | 5.48 | 5.36 |
| 6 | 5.41 | 5.69 | 5.95 | 6.18 | 6.33 | 6.42 | 6.44 | 6.51 | 6.91 | 7.48 | 7.28 | 7.21 | 7.09 | 6.91 |
| 7 | 6.13 | 6.54 | 6.90 | 7.18 | 7.41 | 7.56 | 7.65 | 7.78 | 8.27 | 9.00 | 8.82 | 8.75 | 8.64 | 8.45 |
| 8 | 6.80 | 7.27 | 7.75 | 8.18 | 8.50 | 8.72 | 8.85 | 9.01 | 9.59 | 10.45 | 10.25 | 10.16 | 10.03 | 9.80 |
| 9 | ≈ 7.39 | 7.99 | 8.60 | 9.15 | 9.56 | 9.86 | 10.05 | 10.25 | 10.92 | 11.90 | 11.69 | 11.59 | 11.44 | 11.17 |
| 10 | ≈ 7.74 | 8.66 | 9.40 | 10.08 | 10.59 | 10.97 | 11.24 | 11.48 | 12.24 | 13.35 | 13.13 | 13.03 | 12.86 | 12.56 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 13.134 |
| SC2 | 0 | 8 | 9.011 |
| SC3 | -18 | 7 | 7.283 |
| SC4 | -25 | 6 | 5.946 |
| SC5 | -34 | 6 | 5.472 |
| A | 1857 mm |
|---|---|
| B | 523 mm |
| C | 525 mm |
| F | 345 mm |
| E1 | 517.5 mm |
| E2 | 500 mm |
| E | 1535 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø28 |
| Length | 1857 mm |
|---|---|
| Width | 523 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.