EA-535AC10-C01 C
14.56 kW
Defrost: None
Product code: EA-335AG6-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,693 m³/h |
|---|---|
| Air throw | 10 m |
| External surface | 65.7 m² |
| Inner volume | 19.2 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 97 kg |
| Quantity | 3 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 495 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-335AG6-C01 C | None |
|---|---|
| EA-335AG6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.29 | 6.38 | 6.48 | 6.56 | 6.58 | 6.55 | 6.46 | 6.64 | 7.07 | 7.67 | 7.48 | 7.42 | 7.34 | 7.23 |
| 5 | 7.82 | 8.05 | 8.27 | 8.45 | 8.52 | 8.51 | 8.42 | 8.56 | 9.09 | 9.85 | 9.53 | 9.42 | 9.25 | 8.99 |
| 6 | 9.32 | 9.71 | 10.06 | 10.35 | 10.48 | 10.52 | 10.45 | 10.57 | 11.20 | 12.13 | 11.71 | 11.54 | 11.29 | 10.88 |
| 7 | 10.65 | 11.21 | 11.72 | 12.16 | 12.43 | 12.56 | 12.50 | 12.62 | 13.37 | 14.44 | 13.96 | 13.75 | 13.43 | 12.87 |
| 8 | 11.82 | 12.56 | 13.24 | 13.83 | 14.14 | 14.34 | 14.38 | 14.56 | 15.44 | 16.72 | 16.23 | 15.99 | 15.61 | 14.91 |
| 9 | 12.88 | 13.83 | 14.60 | 15.35 | 15.85 | 16.14 | 16.23 | 16.45 | 17.44 | 18.87 | 18.34 | 18.08 | 17.67 | 16.92 |
| 10 | ≈ 13.85 | 14.85 | 15.97 | 16.89 | 17.53 | 17.92 | 18.08 | 18.33 | 19.44 | 21.04 | 20.46 | 20.17 | 19.70 | 18.85 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 20.459 |
| SC2 | 0 | 8 | 14.563 |
| SC3 | -18 | 7 | 12.288 |
| SC4 | -25 | 6 | 10.055 |
| SC5 | -34 | 6 | 9.413 |
| A | 1857 mm |
|---|---|
| B | 673 mm |
| C | 525 mm |
| F | 495 mm |
| E1 | 517.5 mm |
| E2 | 500 mm |
| E | 1535 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 1857 mm |
|---|---|
| Width | 623 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.