EA-530AE4-C01 C
13.60 kW
Defrost: None
Product code: EA-335AG8-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,029 m³/h |
|---|---|
| Air throw | 10 m |
| External surface | 50.8 m² |
| Inner volume | 19.2 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 96 kg |
| Quantity | 3 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 495 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | B |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-335AG8-C01 C | None |
|---|---|
| EA-335AG8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.77 | 5.81 | 5.86 | 5.90 | 5.89 | 5.84 | 5.76 | 5.89 | 6.26 | 6.78 | 6.61 | 6.56 | 6.48 | 6.38 |
| 5 | 7.27 | 7.42 | 7.57 | 7.69 | 7.73 | 7.71 | 7.62 | 7.73 | 8.20 | 8.87 | 8.59 | 8.49 | 8.34 | 8.13 |
| 6 | 8.74 | 9.03 | 9.29 | 9.49 | 9.61 | 9.63 | 9.56 | 9.65 | 10.22 | 11.06 | 10.69 | 10.53 | 10.31 | 9.94 |
| 7 | 10.07 | 10.53 | 10.94 | 11.30 | 11.50 | 11.58 | 11.52 | 11.63 | 12.32 | 13.32 | 12.87 | 12.68 | 12.39 | 11.91 |
| 8 | 11.26 | 11.88 | 12.44 | 12.94 | 13.26 | 13.38 | 13.43 | 13.60 | 14.42 | 15.58 | 15.08 | 14.86 | 14.51 | 13.92 |
| 9 | 12.33 | 13.13 | 13.86 | 14.42 | 14.85 | 15.10 | 15.20 | 15.40 | 16.34 | 17.70 | 17.21 | 16.98 | 16.62 | 15.98 |
| 10 | 13.31 | 14.30 | 15.12 | 15.91 | 16.46 | 16.81 | 16.96 | 17.21 | 18.25 | 19.77 | 19.25 | 18.99 | 18.59 | 17.88 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 19.247 |
| SC2 | 0 | 8 | 13.602 |
| SC3 | -18 | 7 | 11.396 |
| SC4 | -25 | 6 | 9.292 |
| SC5 | -34 | 6 | 8.816 |
| A | 1857 mm |
|---|---|
| B | 673 mm |
| C | 525 mm |
| F | 495 mm |
| E1 | 517.5 mm |
| E2 | 500 mm |
| E | 1535 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 1857 mm |
|---|---|
| Width | 623 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.