EA-440AC8-C01 C
15.42 kW
Defrost: Electric
Product code: EA-340AC4-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 9,010 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 58.6 m² |
| Inner volume | 12.6 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 85 kg |
| Quantity | 3 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø35 |
| EA-340AC4-C01 C | None |
|---|---|
| EA-340AC4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.39 | 6.42 | 6.45 | 6.47 | 6.44 | 6.38 | 6.29 | 6.41 | 6.81 | 7.35 | 7.15 | 7.08 | 6.97 | 6.82 |
| 5 | 8.25 | 8.43 | 8.58 | 8.68 | 8.70 | 8.65 | 8.54 | 8.66 | 9.19 | 9.93 | 9.63 | 9.54 | 9.40 | 9.20 |
| 6 | 9.89 | 10.25 | 10.57 | 10.86 | 11.02 | 11.09 | 10.99 | 11.08 | 11.74 | 12.69 | 12.28 | 12.13 | 11.92 | 11.59 |
| 7 | 11.31 | 11.86 | 12.28 | 12.70 | 12.96 | 13.10 | 13.12 | 13.29 | 14.12 | 15.32 | 14.92 | 14.77 | 14.54 | 14.17 |
| 8 | 12.62 | 13.29 | 13.97 | 14.55 | 14.93 | 15.14 | 15.21 | 15.41 | 16.36 | 17.76 | 17.29 | 17.10 | 16.82 | 16.35 |
| 9 | 13.74 | 14.70 | 15.58 | 16.35 | 16.88 | 17.18 | 17.31 | 17.55 | 18.63 | 20.22 | 19.71 | 19.48 | 19.15 | 18.58 |
| 10 | 14.82 | 16.02 | 17.13 | 18.10 | 18.77 | 19.21 | 19.41 | 19.71 | 20.93 | 22.71 | 22.16 | 21.91 | 21.52 | 20.86 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 22.161 |
| SC2 | 0 | 8 | 15.408 |
| SC3 | -18 | 7 | 12.822 |
| SC4 | -25 | 6 | 10.574 |
| SC5 | -34 | 6 | 9.982 |
| A | 2017 mm |
|---|---|
| B | 586 mm |
| C | 605 mm |
| F | 395 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 1685 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø35 |
| Length | 2017 mm |
|---|---|
| Width | 586 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.