EA-150AG4-C09 C
13.94 kW
Defrost: Electric
Product code: EA-340AC6-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 9,543 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 42.2 m² |
| Inner volume | 12.6 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 82 kg |
| Quantity | 3 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø35 |
| EA-340AC6-C01 C | None |
|---|---|
| EA-340AC6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.76 | 5.73 | 5.72 | 5.72 | 5.67 | 5.60 | 5.52 | 5.57 | 5.89 | 6.35 | 6.16 | 6.09 | 5.99 | 5.84 |
| 5 | 7.49 | 7.55 | 7.64 | 7.71 | 7.71 | 7.66 | 7.56 | 7.61 | 8.06 | 8.70 | 8.43 | 8.34 | 8.21 | 8.02 |
| 6 | 9.11 | 9.37 | 9.60 | 9.79 | 9.87 | 9.86 | 9.79 | 9.84 | 10.42 | 11.24 | 10.88 | 10.75 | 10.56 | 10.27 |
| 7 | 10.49 | 10.90 | 11.28 | 11.62 | 11.80 | 11.92 | 11.96 | 12.10 | 12.84 | 13.92 | 13.51 | 13.35 | 13.11 | 12.72 |
| 8 | 11.76 | 12.35 | 12.82 | 13.29 | 13.61 | 13.80 | 13.90 | 14.05 | 14.92 | 16.20 | 15.83 | 15.67 | 15.44 | 15.03 |
| 9 | 12.93 | 13.64 | 14.35 | 14.97 | 15.41 | 15.69 | 15.84 | 16.03 | 17.03 | 18.50 | 18.08 | 17.90 | 17.61 | 17.13 |
| 10 | 13.94 | 14.91 | 15.81 | 16.61 | 17.17 | 17.55 | 17.77 | 18.02 | 19.15 | 20.81 | 20.36 | 20.15 | 19.83 | 19.26 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 20.360 |
| SC2 | 0 | 8 | 14.053 |
| SC3 | -18 | 7 | 11.717 |
| SC4 | -25 | 6 | 9.600 |
| SC5 | -34 | 6 | 9.175 |
| A | 2017 mm |
|---|---|
| B | 586 mm |
| C | 605 mm |
| F | 395 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 1685 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø35 |
| Length | 2017 mm |
|---|---|
| Width | 586 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.