EA-163EG10-C01 C
13.29 kW
Defrost: None
Product code: EA-340AC7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 9,698 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 36.7 m² |
| Inner volume | 12.6 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 81 kg |
| Quantity | 3 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø35 |
| EA-340AC7-C01 C | None |
|---|---|
| EA-340AC7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.38 | 5.32 | 5.29 | 5.26 | 5.20 | 5.13 | 5.04 | 5.07 | 5.36 | 5.76 | 5.58 | 5.51 | 5.42 | 5.28 |
| 5 | 7.01 | 7.06 | 7.11 | 7.15 | 7.13 | 7.06 | 6.96 | 6.98 | 7.39 | 7.96 | 7.71 | 7.62 | 7.49 | 7.31 |
| 6 | 8.62 | 8.82 | 8.99 | 9.13 | 9.17 | 9.14 | 9.05 | 9.09 | 9.61 | 10.36 | 10.01 | 9.89 | 9.71 | 9.43 |
| 7 | 10.03 | 10.37 | 10.69 | 10.98 | 11.16 | 11.26 | 11.25 | 11.27 | 11.94 | 12.90 | 12.50 | 12.34 | 12.11 | 11.74 |
| 8 | 11.27 | 11.77 | 12.23 | 12.59 | 12.87 | 13.03 | 13.10 | 13.24 | 14.06 | 15.26 | 14.90 | 14.75 | 14.53 | 14.18 |
| 9 | 12.42 | 13.04 | 13.66 | 14.21 | 14.59 | 14.83 | 14.96 | 15.13 | 16.06 | 17.44 | 17.05 | 16.88 | 16.63 | 16.19 |
| 10 | 13.48 | 14.29 | 15.08 | 15.79 | 16.28 | 16.61 | 16.81 | 17.02 | 18.09 | 19.64 | 19.23 | 19.04 | 18.75 | 18.24 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 19.225 |
| SC2 | 0 | 8 | 13.240 |
| SC3 | -18 | 7 | 11.063 |
| SC4 | -25 | 6 | 8.988 |
| SC5 | -34 | 6 | 8.674 |
| A | 2017 mm |
|---|---|
| B | 586 mm |
| C | 605 mm |
| F | 395 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 1685 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø35 |
| Length | 2017 mm |
|---|---|
| Width | 586 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.