EA-530AE4-C05 C
12.15 kW
Defrost: Electric
Product code: EA-340AC8-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 9,850 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 32.6 m² |
| Inner volume | 12.7 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 81 kg |
| Quantity | 3 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | C |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø35 |
| EA-340AC8-C01 C | None |
|---|---|
| EA-340AC8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.89 | 4.81 | 4.76 | 4.72 | 4.65 | 4.58 | 4.49 | 4.52 | 4.76 | 5.12 | 4.95 | 4.89 | 4.81 | 4.68 |
| 5 | 6.42 | 6.42 | 6.44 | 6.45 | 6.41 | 6.33 | 6.23 | 6.24 | 6.60 | 7.11 | 6.87 | 6.79 | 6.68 | 6.51 |
| 6 | 7.95 | 8.06 | 8.17 | 8.25 | 8.27 | 8.23 | 8.13 | 8.15 | 8.62 | 9.28 | 8.97 | 8.85 | 8.69 | 8.45 |
| 7 | 9.36 | 9.62 | 9.88 | 10.09 | 10.19 | 10.20 | 10.13 | 10.17 | 10.76 | 11.61 | 11.23 | 11.09 | 10.87 | 10.54 |
| 8 | 10.56 | 10.96 | 11.33 | 11.67 | 11.89 | 11.99 | 12.05 | 12.17 | 12.92 | 14.01 | 13.59 | 13.43 | 13.18 | 12.78 |
| 9 | 11.69 | 12.24 | 12.69 | 13.15 | 13.47 | 13.66 | 13.77 | 13.91 | 14.77 | 16.04 | 15.68 | 15.53 | 15.30 | 14.92 |
| 10 | 12.73 | 13.39 | 14.05 | 14.64 | 15.06 | 15.33 | 15.49 | 15.67 | 16.65 | 18.08 | 17.70 | 17.53 | 17.27 | 16.84 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 17.695 |
| SC2 | 0 | 8 | 12.166 |
| SC3 | -18 | 7 | 10.139 |
| SC4 | -25 | 6 | 8.172 |
| SC5 | -34 | 6 | 7.983 |
| A | 2017 mm |
|---|---|
| B | 586 mm |
| C | 605 mm |
| F | 395 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 1685 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø35 |
| Length | 2017 mm |
|---|---|
| Width | 586 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.