EA-440AC8-C01 C
15.42 kW
Defrost: Electric
Product code: EA-340AE8-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 8,792 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 48.6 m² |
| Inner volume | 17.8 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 96 kg |
| Quantity | 3 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-340AE8-C01 C | None |
|---|---|
| EA-340AE8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.35 | 6.38 | 6.42 | 6.45 | 6.42 | 6.35 | 6.24 | 6.37 | 6.76 | 7.30 | 7.10 | 7.03 | 6.91 | 6.73 |
| 5 | 8.09 | 8.27 | 8.44 | 8.58 | 8.61 | 8.57 | 8.46 | 8.58 | 9.10 | 9.83 | 9.51 | 9.40 | 9.25 | 9.04 |
| 6 | 9.78 | 10.15 | 10.48 | 10.74 | 10.88 | 10.88 | 10.80 | 10.91 | 11.56 | 12.50 | 12.07 | 11.91 | 11.68 | 11.31 |
| 7 | 11.26 | 11.80 | 12.30 | 12.73 | 13.01 | 13.16 | 13.15 | 13.30 | 14.09 | 15.26 | 14.77 | 14.58 | 14.28 | 13.80 |
| 8 | 12.56 | 13.30 | 13.98 | 14.49 | 14.89 | 15.13 | 15.22 | 15.42 | 16.38 | 17.78 | 17.33 | 17.13 | 16.83 | 16.33 |
| 9 | 13.74 | 14.59 | 15.49 | 16.26 | 16.78 | 17.11 | 17.27 | 17.53 | 18.61 | 20.20 | 19.72 | 19.49 | 19.14 | 18.55 |
| 10 | 14.82 | 15.92 | 17.00 | 17.95 | 18.64 | 19.09 | 19.31 | 19.64 | 20.86 | 22.65 | 22.13 | 21.87 | 21.49 | 20.80 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 22.125 |
| SC2 | 0 | 8 | 15.423 |
| SC3 | -18 | 7 | 12.861 |
| SC4 | -25 | 6 | 10.475 |
| SC5 | -34 | 6 | 9.875 |
| A | 2017 mm |
|---|---|
| B | 636 mm |
| C | 605 mm |
| F | 445 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 1685 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 2017 mm |
|---|---|
| Width | 636 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.