EA-163EG4-C01 C
17.10 kW
Defrost: None
Product code: EA-340AG10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 8,247 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 53.6 m² |
| Inner volume | 24.5 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 117 kg |
| Quantity | 3 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | B |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EA-340AG10-C01 C | None |
|---|---|
| EA-340AG10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.31 | 7.29 | 7.29 | 7.30 | 7.26 | 7.17 | 7.05 | 7.20 | 7.65 | 8.28 | 8.06 | 7.99 | 7.90 | 7.76 |
| 5 | 9.32 | 9.42 | 9.52 | 9.62 | 9.62 | 9.55 | 9.41 | 9.53 | 10.11 | 10.92 | 10.56 | 10.44 | 10.26 | 10.01 |
| 6 | 11.24 | 11.50 | 11.75 | 11.96 | 12.04 | 12.02 | 11.89 | 11.99 | 12.70 | 13.72 | 13.24 | 13.05 | 12.78 | 12.34 |
| 7 | 13.13 | 13.57 | 13.97 | 14.32 | 14.48 | 14.52 | 14.43 | 14.53 | 15.38 | 16.62 | 16.04 | 15.80 | 15.45 | 14.86 |
| 8 | 14.83 | 15.46 | 16.05 | 16.58 | 16.92 | 17.03 | 16.98 | 17.10 | 18.11 | 19.57 | 18.93 | 18.65 | 18.22 | 17.49 |
| 9 | 16.32 | 17.17 | 17.95 | 18.65 | 19.01 | 19.27 | 19.34 | 19.57 | 20.75 | 22.48 | 21.82 | 21.50 | 21.01 | 20.17 |
| 10 | 17.71 | 18.79 | 19.79 | 20.55 | 21.14 | 21.49 | 21.62 | 21.90 | 23.23 | 25.15 | 24.50 | 24.19 | 23.70 | 22.84 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 24.500 |
| SC2 | 0 | 8 | 17.104 |
| SC3 | -18 | 7 | 14.412 |
| SC4 | -25 | 6 | 11.746 |
| SC5 | -34 | 6 | 11.312 |
| A | 2017 mm |
|---|---|
| B | 686 mm |
| C | 605 mm |
| F | 495 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 1685 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 2017 mm |
|---|---|
| Width | 686 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.