EA-263FC7-C19 C
23.59 kW
Defrost: Electric
Product code: EA-345AC4-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 14,947 m³/h |
|---|---|
| Air throw | 18 m |
| External surface | 79.9 m² |
| Inner volume | 17.6 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 115 kg |
| Quantity | 3 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 1,470 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø42 |
| EA-345AC4-C01 C | None |
|---|---|
| EA-345AC4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 9.75 | 9.79 | 9.83 | 9.85 | 9.78 | 9.66 | 9.51 | 9.65 | 10.22 | 11.01 | 10.69 | 10.57 | 10.40 | 10.16 |
| 5 | 12.64 | 12.94 | 13.19 | 13.37 | 13.37 | 13.28 | 13.10 | 13.23 | 14.02 | 15.13 | 14.67 | 14.51 | 14.29 | 13.97 |
| 6 | 15.06 | 15.61 | 16.11 | 16.54 | 16.74 | 16.85 | 16.85 | 17.08 | 18.14 | 19.60 | 18.98 | 18.75 | 18.42 | 17.91 |
| 7 | 17.21 | 17.97 | 18.72 | 19.38 | 19.79 | 20.01 | 20.06 | 20.31 | 21.57 | 23.39 | 22.81 | 22.58 | 22.25 | 21.71 |
| 8 | 19.10 | 20.26 | 21.31 | 22.22 | 22.83 | 23.18 | 23.31 | 23.60 | 25.06 | 27.20 | 26.51 | 26.23 | 25.81 | 25.13 |
| 9 | 20.90 | 22.41 | 23.79 | 25.00 | 25.84 | 26.35 | 26.59 | 26.94 | 28.61 | 31.06 | 30.29 | 29.96 | 29.47 | 28.65 |
| 10 | ≈ 22.53 | 24.41 | 26.16 | 27.69 | 28.77 | 29.48 | 29.85 | 30.30 | 32.19 | 34.95 | 34.13 | 33.76 | 33.20 | 32.24 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 34.132 |
| SC2 | 0 | 8 | 23.603 |
| SC3 | -18 | 7 | 19.568 |
| SC4 | -25 | 6 | 16.112 |
| SC5 | -34 | 6 | 15.193 |
| A | 2467 mm |
|---|---|
| B | 590 mm |
| C | 645 mm |
| F | 395 mm |
| E1 | 718 mm |
| E2 | 700 mm |
| E | 2135 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø42 |
| Length | 2467 mm |
|---|---|
| Width | 590 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.