EA-163ED4-C11 C
18.95 kW
Defrost: Electric
Product code: EA-345AC7-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 16,020 m³/h |
|---|---|
| Air throw | 19 m |
| External surface | 50.1 m² |
| Inner volume | 17.3 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 109 kg |
| Quantity | 3 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 1,470 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | D |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø42 |
| EA-345AC7-C01 C | None |
|---|---|
| EA-345AC7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.64 | 7.52 | 7.43 | 7.35 | 7.24 | 7.10 | 6.95 | 6.97 | 7.34 | 7.88 | 7.61 | 7.52 | 7.38 | 7.18 |
| 5 | 10.10 | 10.13 | 10.15 | 10.16 | 10.08 | 9.93 | 9.75 | 9.77 | 10.33 | 11.10 | 10.72 | 10.59 | 10.40 | 10.09 |
| 6 | 12.53 | 12.77 | 12.97 | 13.13 | 13.13 | 13.04 | 12.86 | 12.89 | 13.63 | 14.66 | 14.13 | 13.95 | 13.68 | 13.29 |
| 7 | 14.61 | 15.06 | 15.48 | 15.86 | 16.09 | 16.19 | 16.16 | 16.18 | 17.12 | 18.46 | 17.84 | 17.60 | 17.25 | 16.70 |
| 8 | 16.47 | 17.16 | 17.70 | 18.26 | 18.61 | 18.81 | 18.88 | 19.06 | 20.23 | 21.94 | 21.40 | 21.19 | 20.87 | 20.35 |
| 9 | 18.20 | 19.05 | 19.91 | 20.66 | 21.17 | 21.47 | 21.61 | 21.84 | 23.19 | 25.16 | 24.56 | 24.31 | 23.94 | 23.33 |
| 10 | 19.71 | 20.92 | 22.03 | 23.01 | 23.69 | 24.13 | 24.36 | 24.64 | 26.17 | 28.41 | 27.77 | 27.49 | 27.07 | 26.36 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 27.766 |
| SC2 | 0 | 8 | 19.063 |
| SC3 | -18 | 7 | 15.970 |
| SC4 | -25 | 6 | 12.971 |
| SC5 | -34 | 6 | 12.602 |
| A | 2467 mm |
|---|---|
| B | 590 mm |
| C | 645 mm |
| F | 395 mm |
| E1 | 718 mm |
| E2 | 700 mm |
| E | 2135 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø42 |
| Length | 2467 mm |
|---|---|
| Width | 590 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.