EA-180GD10-C01 C
21.95 kW
Defrost: Electric
Product code: EA-345AE10-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 15,099 m³/h |
|---|---|
| Air throw | 18 m |
| External surface | 54.8 m² |
| Inner volume | 25.0 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 127 kg |
| Quantity | 3 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 1,470 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EA-345AE10-C01 C | None |
|---|---|
| EA-345AE10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.89 | 8.93 | 8.97 | 9.00 | 8.94 | 8.83 | 8.67 | 8.77 | 9.30 | 10.00 | 9.67 | 9.54 | 9.36 | 9.09 |
| 5 | 11.45 | 11.64 | 11.88 | 12.07 | 12.13 | 12.08 | 11.94 | 12.04 | 12.76 | 13.76 | 13.31 | 13.15 | 12.93 | 12.62 |
| 6 | 13.79 | 14.32 | 14.79 | 15.19 | 15.40 | 15.44 | 15.36 | 15.49 | 16.42 | 17.74 | 17.17 | 16.95 | 16.63 | 16.12 |
| 7 | 15.85 | 16.63 | 17.34 | 17.97 | 18.39 | 18.58 | 18.69 | 18.94 | 20.12 | 21.83 | 21.19 | 20.94 | 20.55 | 19.90 |
| 8 | 17.68 | 18.75 | 19.61 | 20.47 | 21.08 | 21.46 | 21.65 | 21.96 | 23.34 | 25.36 | 24.78 | 24.53 | 24.15 | 23.49 |
| 9 | 19.36 | 20.61 | 21.86 | 22.98 | 23.78 | 24.31 | 24.61 | 25.00 | 26.57 | 28.88 | 28.26 | 27.97 | 27.53 | 26.77 |
| 10 | 20.88 | 22.44 | 24.00 | 25.38 | 26.41 | 27.12 | 27.55 | 28.03 | 29.81 | 32.42 | 31.76 | 31.44 | 30.95 | 30.09 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 31.760 |
| SC2 | 0 | 8 | 21.961 |
| SC3 | -18 | 7 | 18.165 |
| SC4 | -25 | 6 | 14.794 |
| SC5 | -34 | 6 | 13.922 |
| A | 2467 mm |
|---|---|
| B | 640 mm |
| C | 645 mm |
| F | 445 mm |
| E1 | 718 mm |
| E2 | 700 mm |
| E | 2135 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 2467 mm |
|---|---|
| Width | 640 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.