EA-540AE10-C01 C
24.63 kW
Defrost: None
Product code: EA-350AC7-C09 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 21,102 m³/h |
|---|---|
| Air throw | 22 m |
| External surface | 64.9 m² |
| Inner volume | 23.2 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 137 kg |
| Quantity | 3 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 2,130 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.4 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| EA-350AC7-C09 C | None |
|---|---|
| EA-350AC7-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 9.89 | 9.56 | 9.32 | 9.14 | 8.96 | 8.78 | 8.61 | 8.58 | 9.05 | 9.73 | 9.42 | 9.31 | 9.16 | 8.94 |
| 5 | 13.36 | 13.08 | 12.88 | 12.72 | 12.50 | 12.26 | 11.99 | 11.95 | 12.61 | 13.55 | 13.08 | 12.90 | 12.66 | 12.30 |
| 6 | 16.94 | 16.76 | 16.70 | 16.64 | 16.47 | 16.21 | 15.89 | 15.81 | 16.68 | 17.90 | 17.24 | 17.00 | 16.68 | 16.19 |
| 7 | 20.37 | 20.51 | 20.64 | 20.76 | 20.67 | 20.47 | 20.16 | 20.07 | 21.18 | 22.74 | 21.88 | 21.57 | 21.12 | 20.43 |
| 8 | 23.39 | 23.80 | 24.23 | 24.66 | 24.90 | 24.91 | 24.67 | 24.59 | 25.96 | 27.94 | 26.93 | 26.54 | 25.98 | 25.09 |
| 9 | 26.14 | 26.82 | 27.49 | 28.04 | 28.42 | 28.62 | 28.66 | 28.82 | 30.55 | 33.10 | 32.21 | 31.77 | 31.12 | 30.08 |
| 10 | 28.74 | 29.64 | 30.58 | 31.43 | 31.98 | 32.30 | 32.41 | 32.62 | 34.59 | 37.48 | 36.55 | 36.17 | 35.60 | 34.67 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 36.551 |
| SC2 | 0 | 8 | 24.585 |
| SC3 | -18 | 7 | 20.749 |
| SC4 | -25 | 6 | 16.699 |
| SC5 | -34 | 6 | 16.932 |
| A | 2937 mm |
|---|---|
| B | 590 mm |
| C | 715 mm |
| F | 510 mm |
| E1 | 868 mm |
| E2 | 850 mm |
| E | 2586 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 2937 mm |
|---|---|
| Width | 590 mm |
| Height | 685 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.