EA-550AC6-C09 C
41.95 kW
Defrost: None
Product code: EA-350AG4-C09 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 15,946 m³/h |
|---|---|
| Air throw | 17 m |
| External surface | 206.7 m² |
| Inner volume | 44.0 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 226 kg |
| Quantity | 3 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 2,130 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 62.0 dB(A) |
|---|---|
| Sound power | 84.4 dB(A) |
| Energy class | D |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø54 |
| EA-350AG4-C09 C | None |
|---|---|
| EA-350AG4-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 18.34 | 18.56 | 18.78 | 18.97 | 18.99 | 18.86 | 18.62 | 19.06 | 20.29 | 22.00 | 21.47 | 21.31 | 21.09 | 20.79 |
| 5 | 23.06 | 23.63 | 24.08 | 24.53 | 24.70 | 24.63 | 24.35 | 24.70 | 26.21 | 28.37 | 27.46 | 27.14 | 26.68 | 25.98 |
| 6 | 27.36 | 28.43 | 29.39 | 30.17 | 30.56 | 30.60 | 30.32 | 30.61 | 32.43 | 35.09 | 33.88 | 33.41 | 32.70 | 31.57 |
| 7 | 31.13 | 32.66 | 34.04 | 35.22 | 35.80 | 36.13 | 36.10 | 36.51 | 38.71 | 41.93 | 40.51 | 39.92 | 39.01 | 37.51 |
| 8 | 34.57 | 36.64 | 38.28 | 39.88 | 40.91 | 41.41 | 41.50 | 41.95 | 44.47 | 48.13 | 46.73 | 46.10 | 45.12 | 43.42 |
| 9 | 37.71 | 40.12 | 42.50 | 44.56 | 45.95 | 46.68 | 46.90 | 47.42 | 50.27 | 54.39 | 52.84 | 52.11 | 50.98 | 48.91 |
| 10 | 40.06 | 43.56 | 46.51 | 49.10 | 50.85 | 51.90 | 52.30 | 52.92 | 56.10 | 60.70 | 59.01 | 58.19 | 56.91 | 54.51 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 59.012 |
| SC2 | 0 | 8 | 41.947 |
| SC3 | -18 | 7 | 35.554 |
| SC4 | -25 | 6 | 29.387 |
| SC5 | -34 | 6 | 27.625 |
| A | 2937 mm |
|---|---|
| B | 740 mm |
| C | 715 mm |
| F | 660 mm |
| E1 | 868 mm |
| E2 | 850 mm |
| E | 2586 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø54 |
| Length | 2937 mm |
|---|---|
| Width | 690 mm |
| Height | 685 mm |
Our engineers answer with a selection for your conditions.