EA-363ED4-C01 C
39.94 kW
Defrost: Electric
Product code: EA-350AG6-C09 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 17,109 m³/h |
|---|---|
| Air throw | 19 m |
| External surface | 148.8 m² |
| Inner volume | 43.5 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 209 kg |
| Quantity | 3 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 2,130 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.6 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| EA-350AG6-C09 C | None |
|---|---|
| EA-350AG6-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 17.16 | 17.24 | 17.35 | 17.44 | 17.39 | 17.23 | 16.98 | 17.33 | 18.43 | 19.95 | 19.44 | 19.28 | 19.05 | 18.75 |
| 5 | 21.68 | 22.12 | 22.51 | 22.85 | 22.94 | 22.82 | 22.54 | 22.83 | 24.21 | 26.18 | 25.34 | 25.05 | 24.64 | 24.04 |
| 6 | 26.10 | 26.95 | 27.72 | 28.35 | 28.65 | 28.61 | 28.37 | 28.61 | 30.31 | 32.76 | 31.64 | 31.20 | 30.56 | 29.54 |
| 7 | 29.95 | 31.24 | 32.42 | 33.45 | 34.07 | 34.36 | 34.26 | 34.54 | 36.56 | 39.55 | 38.21 | 37.67 | 36.85 | 35.50 |
| 8 | 33.39 | 35.18 | 36.81 | 38.03 | 38.94 | 39.40 | 39.50 | 39.94 | 42.36 | 45.89 | 44.61 | 44.04 | 43.18 | 41.63 |
| 9 | 36.57 | 38.69 | 40.78 | 42.61 | 43.81 | 44.51 | 44.75 | 45.27 | 48.01 | 52.00 | 50.59 | 49.94 | 48.94 | 47.21 |
| 10 | 39.46 | 42.13 | 44.75 | 47.07 | 48.63 | 49.59 | 49.99 | 50.62 | 53.70 | 58.15 | 56.63 | 55.89 | 54.76 | 52.78 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 56.625 |
| SC2 | 0 | 8 | 39.943 |
| SC3 | -18 | 7 | 33.738 |
| SC4 | -25 | 6 | 27.716 |
| SC5 | -34 | 6 | 26.319 |
| A | 2937 mm |
|---|---|
| B | 740 mm |
| C | 715 mm |
| F | 660 mm |
| E1 | 868 mm |
| E2 | 850 mm |
| E | 2586 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 2937 mm |
|---|---|
| Width | 690 mm |
| Height | 685 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.