EA-350AG10-C09 C
34.56 kW
Defrost: None
Product code: EA-363EC4-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 25,000 m³/h |
|---|---|
| Air throw | 23 m |
| External surface | 200.5 m² |
| Inner volume | 41.2 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 257 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 1,800 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 79.1 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø42 |
| EA-363EC4-C01 C | None |
|---|---|
| EA-363EC4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 14.62 | 14.70 | 14.80 | 14.86 | 14.86 | 14.79 | 14.67 | 14.87 | 15.79 | 17.07 | 16.67 | 16.51 | 16.30 | 15.97 |
| 5 | 18.49 | 18.92 | 19.28 | 19.57 | 19.66 | 19.61 | 19.47 | 19.60 | 20.80 | 22.49 | 21.92 | 21.71 | 21.43 | 20.99 |
| 6 | 22.14 | 22.88 | 23.63 | 24.24 | 24.56 | 24.64 | 24.55 | 24.74 | 26.23 | 28.36 | 27.56 | 27.27 | 26.84 | 26.19 |
| 7 | 25.14 | 26.37 | 27.49 | 28.46 | 29.09 | 29.45 | 29.60 | 29.94 | 31.81 | 34.52 | 33.60 | 33.23 | 32.68 | 31.80 |
| 8 | 27.92 | 29.62 | 31.15 | 32.48 | 33.37 | 33.90 | 34.17 | 34.57 | 36.72 | 39.86 | 38.96 | 38.59 | 38.04 | 37.13 |
| 9 | 30.47 | 32.67 | 34.66 | 36.39 | 37.59 | 38.36 | 38.76 | 39.24 | 41.69 | 45.29 | 44.27 | 43.83 | 43.18 | 42.09 |
| 10 | ≈ 32.77 | 35.50 | 38.00 | 40.19 | 41.74 | 42.75 | 43.34 | 43.95 | 46.71 | 50.75 | 49.64 | 49.15 | 48.41 | 47.15 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 49.641 |
| SC2 | 0 | 8 | 34.568 |
| SC3 | -18 | 7 | 28.748 |
| SC4 | -25 | 6 | 23.628 |
| SC5 | -34 | 6 | 22.365 |
| A | 2815 mm |
|---|---|
| B | 900 mm |
| C | 1190 mm |
| F | 860 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 2435 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø42 |
| Length | 2815 mm |
|---|---|
| Width | 900 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.