EA-263EG4-C01 C
34.55 kW
Defrost: None
Product code: EA-363ED7-C06 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 25,790 m³/h |
|---|---|
| Air throw | 24 m |
| External surface | 168.5 m² |
| Inner volume | 49.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 277 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 890 rpm |
| Power | 1,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 78.1 dB(A) |
| Energy class | C |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EA-363ED7-C06 C | None |
|---|---|
| EA-363ED7-C06 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 14.58 | 14.49 | 14.45 | 14.44 | 14.35 | 14.22 | 14.07 | 14.20 | 15.05 | 16.24 | 15.82 | 15.66 | 15.43 | 15.09 |
| 5 | 18.74 | 18.87 | 18.99 | 19.11 | 19.06 | 18.93 | 18.73 | 18.84 | 19.96 | 21.55 | 20.95 | 20.73 | 20.43 | 19.98 |
| 6 | 22.69 | 23.17 | 23.59 | 23.93 | 24.04 | 23.97 | 23.77 | 23.82 | 25.22 | 27.23 | 26.41 | 26.11 | 25.68 | 25.02 |
| 7 | 26.39 | 27.18 | 27.97 | 28.64 | 28.99 | 29.07 | 28.96 | 29.07 | 30.79 | 33.25 | 32.25 | 31.86 | 31.28 | 30.38 |
| 8 | 29.52 | 30.81 | 31.98 | 33.03 | 33.69 | 34.08 | 34.23 | 34.47 | 36.52 | 39.49 | 38.34 | 37.88 | 37.20 | 36.08 |
| 9 | 32.43 | 34.18 | 35.76 | 37.14 | 38.06 | 38.62 | 38.88 | 39.26 | 41.67 | 45.22 | 44.15 | 43.71 | 43.05 | 41.93 |
| 10 | 35.11 | 37.35 | 39.38 | 41.16 | 42.38 | 43.13 | 43.54 | 44.01 | 46.73 | 50.72 | 49.56 | 49.06 | 48.31 | 47.03 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 12.84 | 12.69 | 12.62 | 12.61 | 12.55 | 12.45 | 12.34 | 12.46 | 13.23 | 14.31 | 13.98 | 13.85 | 13.67 | 13.39 |
| 5 | 16.48 | 16.45 | 16.45 | 16.52 | 16.49 | 16.39 | 16.23 | 16.32 | 17.29 | 18.68 | 18.18 | 18.00 | 17.76 | 17.38 |
| 6 | 20.00 | 20.21 | 20.42 | 20.63 | 20.67 | 20.57 | 20.41 | 20.47 | 21.68 | 23.41 | 22.73 | 22.48 | 22.11 | 21.56 |
| 7 | 23.37 | 23.88 | 24.36 | 24.77 | 24.95 | 24.89 | 24.76 | 24.82 | 26.27 | 28.37 | 27.53 | 27.20 | 26.72 | 25.91 |
| 8 | 26.53 | 27.30 | 28.10 | 28.78 | 29.16 | 29.29 | 29.24 | 29.32 | 31.04 | 33.56 | 32.55 | 32.12 | 31.48 | 30.42 |
| 9 | 29.24 | 30.46 | 31.57 | 32.58 | 33.23 | 33.62 | 33.76 | 33.90 | 35.91 | 38.85 | 37.69 | 37.18 | 36.41 | 35.09 |
| 10 | 31.79 | 33.40 | 34.86 | 36.16 | 37.00 | 37.54 | 37.80 | 38.14 | 40.47 | 43.89 | 42.78 | 42.28 | 41.43 | 39.85 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 49.563 | 42.778 |
| SC2 | 0 | 8 | 34.466 | 29.319 |
| SC3 | -18 | 7 | 28.813 | 24.865 |
| SC4 | -25 | 6 | 23.585 | 20.420 |
| SC5 | -34 | 6 | 22.825 | 20.072 |
| A | 2815 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 2435 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 2815 mm |
|---|---|
| Width | 950 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.