EA-350AG6-C09 C
39.94 kW
Defrost: None
Product code: EA-363ED4-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 23,575 m³/h |
|---|---|
| Air throw | 22 m |
| External surface | 250.1 m² |
| Inner volume | 49.1 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 296 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 1,800 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 79.5 dB(A) |
| Energy class | D |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EA-363ED4-C01 C | None |
|---|---|
| EA-363ED4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 17.09 | 17.18 | 17.25 | 17.37 | 17.36 | 17.27 | 17.12 | 17.41 | 18.52 | 20.05 | 19.61 | 19.46 | 19.21 | 18.83 |
| 5 | 21.57 | 22.03 | 22.43 | 22.75 | 22.84 | 22.77 | 22.55 | 22.81 | 24.21 | 26.16 | 25.47 | 25.23 | 24.90 | 24.40 |
| 6 | 25.80 | 26.61 | 27.43 | 28.10 | 28.43 | 28.48 | 28.32 | 28.57 | 30.28 | 32.75 | 31.79 | 31.42 | 30.90 | 30.10 |
| 7 | 29.37 | 30.76 | 32.01 | 33.10 | 33.78 | 34.15 | 34.25 | 34.61 | 36.69 | 39.70 | 38.52 | 38.06 | 37.37 | 36.28 |
| 8 | 32.63 | 34.55 | 36.27 | 37.75 | 38.72 | 39.28 | 39.50 | 39.94 | 42.40 | 46.02 | 44.87 | 44.41 | 43.72 | 42.56 |
| 9 | 35.62 | 38.10 | 40.34 | 42.29 | 43.61 | 44.38 | 44.75 | 45.28 | 48.08 | 52.17 | 50.90 | 50.36 | 49.54 | 48.16 |
| 10 | ≈ 38.34 | 41.42 | 44.24 | 46.69 | 48.37 | 49.45 | 50.00 | 50.66 | 53.80 | 58.39 | 57.01 | 56.40 | 55.46 | 53.86 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 57.012 |
| SC2 | 0 | 8 | 39.940 |
| SC3 | -18 | 7 | 33.414 |
| SC4 | -25 | 6 | 27.429 |
| SC5 | -34 | 6 | 26.044 |
| A | 2815 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 2435 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 2815 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.