EA-450AG4-C10 C
57.86 kW
Defrost: Electric
Product code: EA-363ED4-C11 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 44,255 m³/h |
|---|---|
| Air throw | 41 m |
| External surface | 250.1 m² |
| Inner volume | 49.1 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 347 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 7,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 72.0 dB(A) |
|---|---|
| Sound power | 95.0 dB(A) |
| Energy class | E |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EA-363ED4-C11 C | None |
|---|---|
| EA-363ED4-C11 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 24.44 | 24.29 | 24.18 | 24.06 | 23.86 | 23.58 | 23.26 | 23.54 | 24.88 | 26.83 | 26.11 | 25.84 | 25.47 | 24.93 |
| 5 | 31.63 | 32.01 | 32.29 | 32.46 | 32.33 | 32.00 | 31.48 | 31.74 | 33.64 | 36.29 | 35.25 | 34.90 | 34.40 | 33.57 |
| 6 | 38.09 | 39.13 | 40.08 | 40.92 | 41.25 | 41.07 | 40.60 | 40.85 | 43.26 | 46.64 | 45.15 | 44.62 | 43.88 | 42.76 |
| 7 | 43.63 | 45.34 | 46.85 | 48.15 | 48.89 | 49.22 | 49.22 | 49.73 | 52.78 | 57.18 | 55.77 | 55.24 | 54.24 | 52.66 |
| 8 | 48.79 | 51.27 | 53.46 | 55.31 | 56.44 | 57.02 | 57.15 | 57.71 | 61.25 | 66.37 | 64.68 | 64.02 | 63.05 | 61.50 |
| 9 | 53.53 | 56.86 | 59.83 | 62.33 | 63.96 | 64.85 | 65.18 | 65.84 | 69.87 | 75.74 | 73.81 | 73.03 | 71.87 | 69.95 |
| 10 | 57.86 | 62.12 | 65.93 | 69.19 | 71.38 | 72.68 | 73.25 | 74.05 | 78.61 | 85.27 | 83.11 | 82.21 | 80.84 | 78.58 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 21.31 | 21.01 | 20.91 | 20.85 | 20.68 | 20.47 | 20.24 | 20.66 | 21.90 | 23.67 | 23.11 | 22.90 | 22.61 | 22.19 |
| 5 | 27.54 | 27.58 | 27.67 | 27.74 | 27.56 | 27.26 | 26.89 | 27.25 | 28.92 | 31.25 | 30.42 | 30.14 | 29.76 | 29.21 |
| 6 | 33.62 | 34.21 | 34.54 | 34.90 | 34.87 | 34.63 | 34.19 | 34.50 | 36.55 | 39.42 | 38.20 | 37.77 | 37.17 | 36.28 |
| 7 | 38.94 | 40.06 | 41.08 | 41.97 | 42.42 | 42.40 | 41.98 | 42.19 | 44.65 | 48.17 | 46.58 | 45.99 | 45.12 | 43.78 |
| 8 | 43.72 | 45.43 | 46.93 | 48.23 | 48.92 | 49.24 | 49.21 | 49.65 | 52.67 | 57.06 | 55.54 | 54.83 | 53.81 | 52.11 |
| 9 | 48.18 | 50.56 | 52.64 | 54.41 | 55.43 | 55.95 | 56.03 | 56.51 | 59.92 | 64.93 | 63.23 | 62.52 | 61.49 | 59.83 |
| 10 | 52.30 | 55.42 | 58.15 | 60.48 | 61.96 | 62.65 | 62.89 | 63.45 | 67.28 | 72.89 | 71.01 | 70.21 | 69.03 | 67.09 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 83.110 | 71.009 |
| SC2 | 0 | 8 | 57.714 | 49.654 |
| SC3 | -18 | 7 | 48.500 | 42.214 |
| SC4 | -25 | 6 | 40.084 | 34.535 |
| SC5 | -34 | 6 | 38.372 | 33.786 |
| A | 2815 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 2435 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 2815 mm |
|---|---|
| Width | 950 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.