EA-263GC4-C19 C
35.98 kW
Defrost: Electric
Product code: EA-363EE7-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 23,906 m³/h |
|---|---|
| Air throw | 22 m |
| External surface | 202.8 m² |
| Inner volume | 60.6 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 294 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 1,800 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 79.4 dB(A) |
| Energy class | C |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EA-363EE7-C01 C | None |
|---|---|
| EA-363EE7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 15.75 | 15.55 | 15.46 | 15.43 | 15.33 | 15.20 | 15.04 | 15.27 | 16.22 | 17.53 | 17.11 | 16.95 | 16.73 | 16.39 |
| 5 | 20.28 | 20.17 | 20.21 | 20.27 | 20.19 | 20.03 | 19.80 | 19.99 | 21.21 | 22.92 | 22.31 | 22.09 | 21.80 | 21.35 |
| 6 | 24.67 | 24.91 | 25.14 | 25.36 | 25.37 | 25.21 | 24.94 | 25.09 | 26.58 | 28.70 | 27.83 | 27.52 | 27.08 | 26.40 |
| 7 | 28.88 | 29.50 | 30.06 | 30.53 | 30.70 | 30.62 | 30.32 | 30.44 | 32.21 | 34.78 | 33.68 | 33.27 | 32.66 | 31.70 |
| 8 | 32.85 | 33.78 | 34.74 | 35.54 | 35.95 | 36.04 | 35.86 | 35.99 | 38.10 | 41.16 | 39.84 | 39.32 | 38.55 | 37.32 |
| 9 | 36.26 | 37.75 | 39.11 | 40.32 | 41.08 | 41.49 | 41.48 | 41.67 | 44.12 | 47.68 | 46.21 | 45.61 | 44.70 | 43.22 |
| 10 | 39.44 | 41.42 | 43.21 | 44.78 | 45.77 | 46.35 | 46.57 | 46.99 | 49.85 | 54.02 | 52.66 | 52.01 | 50.98 | 49.26 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 52.658 |
| SC2 | 0 | 8 | 35.992 |
| SC3 | -18 | 7 | 30.628 |
| SC4 | -25 | 6 | 25.144 |
| SC5 | -34 | 6 | 24.759 |
| A | 2815 mm |
|---|---|
| B | 1000 mm |
| C | 1190 mm |
| F | 960 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 2435 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 2815 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.