EA-463FE4-C19 C
81.47 kW
Defrost: None
Product code: EA-363FG4-C08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 38,653 m³/h |
|---|---|
| Air throw | 36 m |
| External surface | 500.6 m² |
| Inner volume | 99.8 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 482 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 5,700 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 74.0 dB(A) |
|---|---|
| Sound power | 97.0 dB(A) |
| Energy class | E |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø66,7 |
| EA-363FG4-C08 C | None |
|---|---|
| EA-363FG4-C08 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 35.60 | 35.60 | 35.62 | 35.79 | 35.72 | 35.47 | 35.09 | 35.77 | 38.05 | 41.22 | 40.33 | 40.03 | 39.63 | 38.93 |
| 5 | 44.98 | 45.64 | 46.23 | 46.73 | 46.80 | 46.49 | 45.97 | 46.57 | 49.41 | 53.45 | 51.98 | 51.47 | 50.76 | 49.70 |
| 6 | 53.92 | 55.50 | 56.59 | 57.70 | 58.15 | 58.07 | 57.52 | 58.04 | 61.50 | 66.47 | 64.36 | 63.58 | 62.46 | 60.72 |
| 7 | 61.76 | 64.22 | 66.45 | 68.40 | 69.57 | 69.99 | 69.55 | 70.04 | 74.17 | 80.18 | 77.53 | 76.49 | 74.96 | 72.51 |
| 8 | 68.78 | 72.25 | 75.38 | 78.08 | 79.76 | 80.60 | 80.68 | 81.49 | 86.42 | 93.66 | 91.04 | 89.95 | 88.04 | 84.91 |
| 9 | 75.27 | 79.87 | 84.00 | 87.54 | 89.86 | 91.06 | 91.38 | 92.31 | 97.88 | 106.02 | 103.10 | 101.82 | 99.90 | 96.64 |
| 10 | 81.20 | 86.99 | 92.24 | 96.76 | 99.76 | 101.51 | 102.12 | 103.22 | 109.46 | 118.53 | 115.32 | 113.86 | 111.65 | 107.87 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | 30.47 | 32.43 | 35.18 | 34.45 | 34.21 | 33.88 | 33.43 |
| 5 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | 41.48 | 44.91 | not rated | not rated | not rated | 41.81 |
| 6 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 7 | not rated | not rated | 56.29 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 8 | not rated | not rated | 64.63 | 66.43 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 9 | not rated | not rated | 72.18 | 74.58 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 10 | not rated | not rated | 79.49 | 82.58 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 115.324 | — |
| SC2 | 0 | 8 | 81.485 | — |
| SC3 | -18 | 7 | 68.952 | — |
| SC4 | -25 | 6 | 56.588 | — |
| SC5 | -34 | 6 | 54.339 | — |
| A | 3415 mm |
|---|---|
| B | 1100 mm |
| C | 1190 mm |
| F | 1060 mm |
| G | 1135 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 3035 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø66,7 |
| Length | 3415 mm |
|---|---|
| Width | 1100 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.