EA-250BC7-C10 C
18.02 kW
Defrost: Electric
Product code: EA-435AE6-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 8,454 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 65.7 m² |
| Inner volume | 19.2 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 102 kg |
| Quantity | 4 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 660 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 76.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-435AE6-C01 C | None |
|---|---|
| EA-435AE6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.64 | 7.72 | 7.80 | 7.87 | 7.88 | 7.82 | 7.72 | 7.88 | 8.39 | 9.08 | 8.86 | 8.79 | 8.70 | 8.57 |
| 5 | 9.67 | 9.92 | 10.11 | 10.30 | 10.38 | 10.36 | 10.26 | 10.41 | 11.04 | 11.95 | 11.59 | 11.46 | 11.28 | 11.01 |
| 6 | 11.53 | 12.00 | 12.42 | 12.77 | 12.95 | 13.00 | 12.91 | 13.05 | 13.84 | 14.98 | 14.50 | 14.31 | 14.03 | 13.59 |
| 7 | 13.17 | 13.83 | 14.44 | 14.97 | 15.24 | 15.43 | 15.48 | 15.68 | 16.65 | 18.07 | 17.52 | 17.29 | 16.94 | 16.36 |
| 8 | 14.65 | 15.55 | 16.27 | 16.98 | 17.46 | 17.73 | 17.83 | 18.07 | 19.19 | 20.82 | 20.28 | 20.04 | 19.68 | 19.05 |
| 9 | 16.00 | 17.04 | 18.08 | 19.00 | 19.62 | 20.01 | 20.19 | 20.48 | 21.74 | 23.58 | 23.00 | 22.73 | 22.31 | 21.55 |
| 10 | 17.22 | 18.52 | 19.81 | 20.95 | 21.75 | 22.28 | 22.54 | 22.89 | 24.31 | 26.37 | 25.75 | 25.44 | 24.97 | 24.09 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 25.747 |
| SC2 | 0 | 8 | 18.072 |
| SC3 | -18 | 7 | 15.121 |
| SC4 | -25 | 6 | 12.416 |
| SC5 | -34 | 6 | 11.649 |
| A | 2357 mm |
|---|---|
| B | 573 mm |
| C | 525 mm |
| F | 395 mm |
| E1 | 517.5 mm |
| E2 | 500 mm |
| E | 2035 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 2357 mm |
|---|---|
| Width | 573 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.